Fresno West Annex Pre-Opening Insp Rpt 23-24 II (2023-2024 inspection cycle)
Read the report at Fresno West Annex Pre-Opening Insp Rpt 23-24 II ↗
December 2, 2024
John Zanoni, Sheriff
Fresno County Sheriff’s Office
2200 Fresno Street
Fresno, CA 93721
SUBJECT: COUNTY OF FRESNO – FRESNO COUNTY SHERIFF’S OFFICE WEST
ANNEX JAIL – SB 1022 BSCC PLAN REVIEW NUMBER 019.0706.01 A31-132
Dear Sheriff Zanoni,
On Wednesday, October 30, 2024, BSCC staff conducted a pre-opening inspection of the
newly constructed West Annex Jail. The purpose of this inspection was to determine
compliance with the applicable Minimum Standards for Local Detention Facilities as
outlined in Titles 15 and 24, California Code of Regulations (CCR). The 2008 version of
Title 24 Regulations was applied as these regulations were in effect at the time of the
original submittal of the project.
The inspection report includes this letter, a Physical Plant Evaluation outlining Title 24
requirements for the facility design and furnishings, and a Living Area Space Evaluation
that summarizes the facility’s configuration and rated capacity. We encourage the practice
of maintaining a permanent file for historical copies of all inspections and this file should
be the first point of reference when preparing for all future inspections.
No issues of noncompliance were identified during the inspection relating to the Facilities
Standards and Operations (FSO) division of the BSCC. However, since this facility was
constructed with the assistance of the Adult Local Criminal Justice Facilities Construction
(SB1022) grant, a final inspection by the BSCC’s County Facilities Construction (CFC)
division is required prior to populating the facility.
We would like to acknowledge the efforts of everyone with whom we have interacted with
during the entire planning and construction process. The result is the culmination of their
efforts in successfully constructing a facility that will serve the needs of your community
for many years.
This concludes the pre-opening inspection report. We very much appreciate your
commitment to operate safe and secure detention facilities in compliance with the
California Code of Regulations. Should you have any questions or comments relating to
this inspection, please contact me directly at (916) 956-1559 or by e-mail at
tim.mcwilliams@bscc.ca.gov.
John Zanoni
Sheriff
Page 2
Sincerely,
TIM MCWILLIAMS
Field Representative
Facilities Standards and Operations Division
Enclosures
Cc: County Administrative Officer, County of Fresno*
Chair, Board of Supervisors, County of Fresno*
Presiding Judge, Superior Court, County of Fresno*
Grand Jury Foreperson, Superior Court, County of Fresno*
Adam Esmay, Captain, Fresno County Sheriff’s Office (electronic copy)
Michelle LeFors, Inmate Services Director, Fresno County Sheriff's Office
(electronic copy)
Phillip Hurt, Sergeant, Fresno County Sheriff’s Office (electronic copy)
Tonya Parker-Mashburn, Field Representative, BSCC, County Facilities
Construction Division (electronic copy)
*Copy provided upon request
0706 Fresno West Annex Pre-Opening LTR 10.30.2024
ADULT TYPE I, II, III AND IV FACILITIES
PHYSICAL PLANT EVALUATION
The Board of State and Community Corrections
APPLICABLE TITLE 24 REGULATIONS: 6/94; 2/99; 2001; 2005; 2008; 2010; 2013; 2017; 2019
BSCC Code: 0706
FACILITY NAME: Fresno County, West Annex Jail FACILITY TYPE: II
2008
APPLICABLE REGULATIONS
(Check All That Apply):
FIELD REPRESENTATIVE: Tim McWilliams DATE: 10/30/24
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.1 RECEPTION AND BOOKING Transfer facility only. No intake/booking
conducted at this facility.
Facilities where booking and housing occur shall have
the following space and equipment: ☐ ☐ ☒
1. Weapons locker as specified in Section
1231.3.12.
2. A cell or room for the confinement of inmates
pending their booking, complying with Section
☐ ☐ ☒
1231.2.2.
3. A sobering cell as described in Section 1231.2.4
if intoxicated, inmates who may pose a danger to
☐ ☐ ☒
themselves or others are held.
For those facilities that accept male and female
intoxicated inmates two sobering cells shall be
☐ ☐ ☒
provided.
4. Access to a shower within the secure portion of
the facility. ☐ ☐ ☒
5. Provide access to a secure vault or storage
space for inmate valuables. ☐ ☐ ☒
1231.2.2 TEMPORARY HOLDING CELL OR
ROOM
A temporary holding cell or room shall: ☒ ☐ ☐
1. Contain a minimum of 10 square feet (0.93 m2)
of floor area per inmate;
2. Be limited to no more than 16 inmates;
☒ ☐ ☐
3. Be no smaller than 40 square feet (3.7 m2) and
have a clear ceiling height of 8 feet (2438 mm) or
☒ ☐ ☐
more;
4. Contain seating to accommodate all inmates as
required in Section 1231.3; ☒ ☐ ☐
5. Contain a toilet, wash basin and drinking
fountain as specified in Section 1231.3; ☒ ☐ ☐
0706 Fresno West Annex PHY 23-24 Page 1 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
6. Maximize visual supervision of inmates by staff;
and ☒ ☐ ☐
7. When located in a temporary holding facility, the
cell or room shall be equipped with a bunk if
☐ ☐ ☒
inmates are to be held longer than 12 hours.
1231.2.3 TEMPORARY STAGING CELL OR No Temporary Staging cells at this facility.
ROOM
A temporary staging cell or room shall:
1. Be constructed for the purpose of holding ☐ ☐ ☒
inmates who have been classified and segregated
in accordance with Sections 1050 and 1053 of Title
15, Division 1, California Code of Regulations.
2. Be limited to holding inmates up to four hours.
☐ ☐ ☒
3. Be limited to no more than 80 inmates.
☐ ☐ ☒
4. Contain a minimum of 10 square feet (0.93 m2)
of floor area per inmate and a clear ceiling height
☐ ☐ ☒
of 8 feet (2438 mm) or more.
5. Be no smaller than 160 square feet (14.9 m2).
☐ ☐ ☒
6. Contain seating to accommodate all inmates as
required in Section 1231.3. ☐ ☐ ☒
7. Contain toilet, wash basin and drinking fountain
as specified in Section 1231.3. ☐ ☐ ☒
8. Maximize visual supervision of inmates by staff.
☐ ☐ ☒
1231.2.4 SOBERING CELL No Sobering cells at this facility.
A sobering cell shall:
☐ ☐ ☒
1. Contain a minimum of 20 square feet (1.9 m2) of
floor area per inmate;
2. Be limited to eight inmates;
☐ ☐ ☒
3. Be no smaller than 60 square feet (5.6 m2) and
have a clear ceiling height of 8 feet (2438 mm) or
☐ ☐ ☒
more;
4. Contain a toilet, wash basin and drinking
fountain as specified in Section 1231.3; ☐ ☐ ☒
5. Have padded partitions located next to toilet
fixture in such a manner that they provide support
☐ ☐ ☒
to the user;
6. Maximize visual supervision of inmates by staff;
☐ ☐ ☒
7. Be padded on the floor as specified in Section
1231.3; and, ☐ ☐ ☒
8. Have accessible a shower in the secure portion
of the facility. ☐ ☐ ☒
0706 Fresno West Annex PHY 23-24 Page 2 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.5 SAFETY CELL
A safety cell shall:
1. Contain a minimum of 48 square feet (4.5 m2) of
☒ ☐ ☐
floor area with no one floor dimension being less
than 6 feet (1829 mm) and a clear ceiling height of
8 feet (2438 mm) or more;
2. Be limited to one inmate;
☒ ☐ ☐
3. Contain a flushing ring toilet, capable of
accepting solid waste, mounted flush with the floor,
the controls for which must be located outside of ☒ ☐ ☐
the cell;
4. Be padded as specified in Section 1231.3;
☒ ☐ ☐
5. Be equipped with a variable intensity, security-
type lighting fixture which is inaccessible to the
inmate occupant, control of which is located ☒ ☐ ☐
outside of the cell;
6. Provide one or more vertical view panels not
more than 4 inches (102 mm) wide nor less than 24
inches (610 mm) long which shall provide a view of ☒ ☐ ☐
the entire room;
7. Provide a food pass with lockable shutter, no
more than 4 inches (102 mm) high, and located
between 26 inches (660 mm) and 32 inches (813
☒ ☐ ☐
mm) as measured from the bottom of the food pass
to the floor; and,
8. Any wall or ceiling mounted devices must be
inaccessible to the inmate occupant. ☒ ☐ ☐
1231.2.6 SINGLE-OCCUPANCY CELLS
Single-occupancy cells shall: ☒ ☐ ☐
1. Have a maximum capacity of one inmate;
2. Contain a minimum of 60 square feet (5.6 m2) of
floor area in Type I facilities and 70 square feet (6.5
☒ ☐ ☐
m2) of floor area in Type II and Type III facilities;
3. Have a minimum clear ceiling height of 8 feet
(2438 mm) and a minimum width of 6 feet (1829
☒ ☐ ☐
mm);
4. Contain a toilet, wash basin and drinking
fountain as specified in Section 1231.3; and ☒ ☐ ☐
5. Contain a bunk, desk and seat as specified in
Section 1231.3.
Exception: A Type I facility does not require a desk ☒ ☐ ☐
and seat.
1231.2.7 DOUBLE-OCCUPANCY CELLS
Double-occupancy cells shall: ☒ ☐ ☐
1. Have a maximum capacity of two inmates;
0706 Fresno West Annex PHY 23-24 Page 3 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
2. Contain a minimum of 60 square feet (5.6 m2) of
floor area in Type I facilities and 70 square feet (6.5
☒ ☐ ☐
m2) of floor area in Type II and Type III facilities;
3. Have a minimum clear ceiling height of 8 feet
(2438 mm) and a minimum width of 6 feet (1829
☒ ☐ ☐
mm);
4. Contain a toilet, wash basin and drinking
fountain as specified in Section 1231.3; and ☒ ☐ ☐
5. Contain two bunks, and at least one desk and
seat as specified in Section 1231.3.
Exception: A Type I facility does not require a desk ☒ ☐ ☐
and seat.
1231.2.8 DORMITORIES No dormitories located at this facility.
Dormitories shall:
1. Contain a minimum of 50 square feet (4.7 m2) of
floor area per inmate for a single-bed unit; a
☐ ☐ ☒
minimum of 70 square feet (7 m2) for a double-bed
unit; and a minimum of 90 square feet (9.3 m2) for
triple-bed unit and have a minimum ceiling height
of 8 feet (2438 mm);
2. Be designed for no more than 64 inmates and no
fewer than four inmates; ☐ ☐ ☒
3. Provide access to water closets separate from
the wash basin and drinking fountains as specified
☐ ☐ ☒
in Section 1231.3; and
4. In other than Type I facilities, provide storage
space for personal items and clothing for each
☐ ☐ ☒
occupant.
1231.2.9 DAYROOMS
Dayrooms or dayroom space shall:
☒ ☐ ☐
1. Contain 35 square feet (3.3 m2) of floor area per
inmate in width in front of cells/rooms;
2. Contain tables and seating to accommodate the
maximum number of inmates; ☒ ☐ ☐
3. Provide access to water closets, wash basins
and drinking fountains as specified in Section
☒ ☐ ☐
1231.3;
4. Provide access to a shower or showers as
specified in Section 1231.3; and ☒ ☐ ☐
5. Be provided to all inmates in Type II and Type III
facilities (except those housed in special-use cells)
and to inmate workers in Type I facilities. Dayroom
space as described in this section may be a part of
a single occupancy cell used for administrative ☒ ☐ ☐
segregation or a dormitory, in which case the floor
area of the cell or a dormitory must be increased by
the square footage required for the dayroom.
0706 Fresno West Annex PHY 23-24 Page 4 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.10 EXERCISE AREA
An outdoor exercise area or areas must be provided in
every Type II and Type III facility. The minimum clear
height must be 15 feet (4572 mm) and the minimum
☒ ☐ ☐
number of square feet of surface area will be computed
by multiplying 80 percent of maximum rated population
by 50 square feet (4.7 m2) and dividing the result by the
number of one-hour exercise periods per day.
The exercise area must contain or provide free access
to a toilet, wash basin, and drinking fountain as
☒ ☐ ☐
provided in Section 1231.3.
There must be at least one exercise area of not less
than 600 square feet (55.7 m2). The design shall
facilitate security and supervision appropriate to the ☒ ☐ ☐
level of custody.
Type IV facilities shall have an outdoor recreation area
or access to community recreation facilities. ☐ ☐ ☒
1231.2.11 CORRECTIONAL PROGRAM/
MULTIPURPOSE SPACE
An area for correctional programming must be provided
☒ ☐ ☐
in every Type II and Type III facility. The program area
and furnishings shall be designed to meet the needs
specified by the facility’s program statement.
Type IV facilities shall have multipurpose space for
games and activities, dining, visiting, TV meetings and
quiet space for study and reading, such that activities ☐ ☐ ☒
do not conflict with each other.
1231.2.12 MEDICAL EXAMINATION ROOM
There must be a minimum of one suitably equipped
medical examination room in every facility which
provides on-site health care. The examination room ☒ ☐ ☐
shall be designed in consultation with the responsible
physician/health authority.
Such a medical examination room shall:
1. Be located within the security area and provide
for privacy of the inmates; ☒ ☐ ☐
2. Provide not less than 100 square feet (9.3 m2) of
floor space with no single dimension less than 7
☒ ☐ ☐
feet (2134 mm);
3. Provide hot and cold running water;
☒ ☐ ☐
4. Provide lockable storage for medical supplies;
☒ ☐ ☐
5. Provide an examination table;
☒ ☐ ☐
6. Provide adequate lighting; and
☒ ☐ ☐
7. Any room where medical procedures are
provided must be equipped with hot and cold
☒ ☐ ☐
running water
0706 Fresno West Annex PHY 23-24 Page 5 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.13 PHARMACEUTICAL STORAGE SPACE
Provide lockable storage space for medical supplies
☒ ☐ ☐
and pharmaceutical preparations as referenced by Title
15, California Code of Regulations, Section 1216.
1231.2.14 MEDICAL CARE HOUSING Medical care housing is provided at an
adjacent facility.
There shall be some means to provide medical care ☐ ☐ ☒
and housing of ill and/or infirm inmates.
When the program statement for a Type II or Type III
facility indicates that medical care housing is needed,
such housing must provide lockable storage space for
medical instruments and must be located within the ☐ ☐ ☒
security area of the facility accessible to both female
and male inmates, but not in the living area of either.
The medical care housing unit shall be designed in
consultation with the health authority. ☐ ☐ ☒
Medical/mental health areas may contain other than
single occupancy cells. ☐ ☐ ☒
If negative pressure isolation rooms are being planned,
they shall be designed to recognized industry
☐ ☐ ☒
standards.
1231.2.16 COMMISSARY
In all Type II, III and IV facilities, except where
community access is available, there shall be
☒ ☐ ☐
provisions made for inmates to purchase items (such
as candy, toilet articles, stationery supplies, books,
newspapers and magazines, etc.).
An area shall be provided for the secure storage of the
stock for such inmate canteen items. ☒ ☐ ☐
1231.2.17 DINING FACILITIES Meals are served in the housing areas.
In all Type II, III and IV facilities which serve meals,
☐ ☐ ☒
dining areas shall be provided which will allow groups
of inmates to dine together.
Such dining areas shall not contain toilets, wash basins
or showers in the same room without appropriate visual
☐ ☐ ☒
barrier.
Wherever the facility contains a central dining room or
rooms, it shall contain a minimum of 15 square feet (1.4
m2) of floor space and sufficient tables and seating for ☐ ☐ ☒
each inmate being fed.
1231.2.18 VISITING SPACE
Space shall be provided in all Types I, II, III and IV ☒ ☐ ☐
facilities for in-person visiting.
0706 Fresno West Annex PHY 23-24 Page 6 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.19 SAFETY EQUIPMENT STORAGE
A secure area shall be provided for the storage of
safety equipment such as fire extinguishers, self- ☒ ☐ ☐
contained breathing apparatus, wire and barcutters,
emergency lights, etc.
1231.2.20 JANITORS’ CLOSET
In Type II facilities, at least one securely lockable
janitors’ closet with sufficient area for the storage of ☒ ☐ ☐
cleaning implements and supplies must be provided
within the security areas of the facility
A mop sink shall also be available within the security
area of the facility. In court holding, temporary holding,
Types I, III and IV facilities, the closet need not be in ☒ ☐ ☐
the security area.
1231.2.21 STORAGE ROOMS
One or more storage rooms shall be provided to
accommodate a minimum of 80 cubic feet (2.3 m3) of
storage area per inmate for inmate clothing and
personal property, institutional clothing, bedding and ☒ ☐ ☐
supplies. Court holding, temporary holding and Type I
facilities may be excluded from the storage space
requirement for personal and institutional clothing
unless clothing is issued.
1231.2.22 AUDIO MONITORING SYSTEM
In court holding, temporary holding, Type I, Type II and
Type II facilities there shall be an inmate- or sound-
actuated audio monitoring system in temporary holding
cells or rooms, temporary staging cells or rooms,
☒ ☐ ☐
sobering cells, safety cells, single and double
occupancy cells, dormitories, dayrooms, exercise
areas and correctional program/multipurpose space,
which is capable of alerting personnel who can respond
immediately.
1231.2.23 LAUNDRY FACILITIES Laundry service is conducted at another
facility.
In Type IV facilities, provision shall be made for
washing and drying personal clothing by machines, ☐ ☐ ☒
either in the facility or in the community, if access is
permitted for same.
1231.2.24 EMERGENCY POWER
There shall be a source of emergency power in all
detention facilities capable of providing minimal lighting
☒ ☐ ☐
in all housing units, activities areas, corridors, stairs
and central control points, and to maintain fire and life
safety, security, communications and alarm systems.
Such an emergency power source shall conform to the
requirements specified in Title 24, Part 3, Article 700,
California Electrical Code, California Code of ☒ ☐ ☐
Regulations.
0706 Fresno West Annex PHY 23-24 Page 7 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.2.25 CONFIDENTIAL INTERVIEW ROOMS
There must be a minimum of one suitably furnished
interview room for confidential interviews in every
facility which provides onsite health care. The interview ☒ ☐ ☐
room shall be designed in consultation with responsible
custodial staff and health care staff.
Such an interview room shall:
1. Be located within the security area accessible to
both female and male inmates; and ☒ ☐ ☐
2. Provide not less than 70 square feet (6.5 m2) of
floor space with no single dimension less than 6
☒ ☐ ☐
feet (1829 mm).
1231.2.26 ATTORNEY INTERVIEW SPACE
All facilities except Type IV facilities shall include
☒ ☐ ☐
attorney interview areas which provide for confidential
consultation with inmates.
1231.3.1 TOILETS/URINALS
1. Toilets/urinals must be provided in single- ☒ ☐ ☐
occupancy cells and double-occupancy cells.
2. In dormitories, toilets/urinals must be provided in
a ratio to inmates of 1:10. ☒ ☐ ☐
3. Toilets/urinals must be accessible to the
occupants of day-rooms and exercise areas. ☒ ☐ ☐
4. In temporary holding cells and temporary staging
cells toilets/urinals must be provided in a ratio to
☒ ☐ ☐
inmates of 1:16.
5. In sobering cells toilets/urinals must be provided
in a ratio to inmates of 1:8. ☒ ☐ ☐
6. One urinal or 2 feet (610 mm) of urinal trough
may be substituted for each toilet up to one third of
the total number of toilets required, except in those ☐ ☐ ☒
facilities or portions thereof used for females.
7. Toilet areas shall provide modesty for inmates
with staff being able to visually supervise. ☒ ☐ ☐
1231.3.2 WASH BASINS
1. Wash basins must be provided in single ☒ ☐ ☐
occupancy cells and double occupancy cells.
2. In dormitories, wash basins must be provided in
a ratio to inmates of 1:10. ☐ ☐ ☒
3. Wash basins must be accessible to the
occupants of day-rooms and exercise areas ☒ ☐ ☐
4. In temporary holding cells and temporary staging
cells, wash basins must be provided in a ratio to
☒ ☐ ☐
inmates of 1:16.
0706 Fresno West Annex PHY 23-24 Page 8 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
5. In sobering cells, wash basins must be provided
in a ratio to inmates of 1:8. ☐ ☐ ☒
6. Wash basins must be provided with hot and cold
or tempered water. ☒ ☐ ☐
7. Two feet (610 mm) of wash basin trough may be
substituted for each basin required. ☐ ☐ ☒
1231.3.3 DRINKING FOUNTAINS
There must be a minimum of one drinking fountain in
every single-occupancy cell, double-occupancy cell,
☒ ☐ ☐
dormitory, temporary holding cell, temporary staging
cell, sobering cell, and be accessible to the occupants
of day rooms and exercise areas.
Additional drinking fountains shall be located in other
areas of the facility so that drinking water will be
☒ ☐ ☐
available to inmates and staff.
Such drinking fountains must meet the following
minimum health requirements:
1. The drinking fountain bubbler shall be on an
☒ ☐ ☐
angle which prevents waste water from flowing
over the drinking fountain bubbler.
2. Water flow shall be actuated by mechanical
means. ☒ ☐ ☐
1231.3.4 SHOWERS
Must be available to all inmates on a ratio of at least
☒ ☐ ☐
one shower to every 20 inmates or fraction thereof and
must provide hot and cold water or tempered water.
Shower stalls/shower areas must be designed and
constructed of materials which are impervious to water
☒ ☐ ☐
and soap so they may be easily cleaned.
Shower areas shall provide modesty for inmates with
staff being able to visually supervise. ☒ ☐ ☐
1231.3.5 BEDS
Must be elevated off the floor, have a solid bottom, and
☒ ☐ ☐
a sleeping surface of at least 30 inches (762 mm) wide
and 76 inches (1930 mm) long.
Multiple beds must have a minimum of 21 inches (533
mm) between bed pans. ☒ ☐ ☐
Except in minimum security areas, beds must be
securely fastened to the floor or the wall. ☒ ☐ ☐
1231.3.6 LIGHTING
Lighting in housing units, dayrooms and activity areas
must be sufficient to permit easy reading by a person
☒ ☐ ☐
with normal vision, and shall not be less than 20
footcandles (215.2 lux) at desk level and in the
grooming area.
0706 Fresno West Annex PHY 23-24 Page 9 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
Lighting shall be centrally controlled and/or occupant
controlled in housing cells or rooms. ☒ ☐ ☐
Night lighting in these areas shall be sufficient to give
good visibility for purposes of supervision ☒ ☐ ☐
In minimum-security areas, lighting may be supplied by
ordinary lighting fixtures, and in areas of higher
☒ ☐ ☐
security, light fixtures must be of secure design.
1231.3.7 WINDOWS
In housing areas of higher than minimum security,
exterior windows which are constantly accessible to
☒ ☐ ☐
inmates for escape must be designed and constructed
so that if broken out, the net area accessible for escape
is no greater than 5 inches (127 mm) in one dimension.
1231.3.8 CELL PADDING No sobering cell at this facility.
In sobering cells, the floor and partition shall be ☐ ☐ ☒
padded.
In safety cells, padding must cover the entire floor,
doors, and walls and everything on them to a clear
☒ ☐ ☐
height of 8 feet (2438 mm).
All such padded cells must be equipped with a tamper
resistant fire sprinkler as approved by the State Fire
Marshal. ☒ ☐ ☐
All padding must be:
1. Approved for use by the State Fire Marshal;
☒ ☐ ☐
2. Nonporous to facilitate cleaning;
☒ ☐ ☐
3. At least 1/2-inch (12.7 mm) thick;
☒ ☐ ☐
4. Of a unitary or laminated construction to prevent
its destruction by teeth, hand tearing or small metal
☒ ☐ ☐
objects;
5. Firmly bonded to all padded surfaces to prevent
tearing or ripping; and ☒ ☐ ☐
6. Without any exposed seams susceptible to
tearing or ripping. ☒ ☐ ☐
1231.3.9 MIRRORS
A mirror of a material appropriate to the level of security
☒ ☐ ☐
must be provided near each wash basin specified in
these regulations.
1231.3.10 SEATING
In temporary holding and temporary staging cells, ☒ ☐ ☐
seating must be securely fixed to the floor and/or wall.
When bench seating is used, 18 inches (457 mm) of
bench is seating for one person. ☒ ☐ ☐
0706 Fresno West Annex PHY 23-24 Page 10 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
TITLE 24 SECTION YES NO N/A COMMENTS
1231.3.11 TABLE/SEAT
In single- and double-occupancy cells, a table and seat
for the purpose of writing and dining shall be provided. ☒ ☐ ☐
Exception: A Type I facility does not require a table
and a seat.
1231.3.12 WEAPONS LOCKER
A secure weapons locker shall be located outside the ☒ ☐ ☐
security perimeter of the facility
Such weapons lockers shall be equipped with
individual compartments, each with an individual
☒ ☐ ☐
locking device.
Weapons lockers are required in temporary and court
holding facilities and in all facilities of higher than
☒ ☐ ☐
minimum security.
13-102(c)6 DESIGN REQUIREMENTS
Design requirements as specified in Title 24, Part 1, 13-
102(c)6 are met. (See regulation for specific
☒ ☐ ☐
requirements. Note areas of non-compliance that are
applicable to the facility type and construction date in
the "comments" section.)
0706 Fresno West Annex PHY 23-24 Page 11 of 11 A383 PHY Type I-IV (23-24).dot (rev.12/23)
ADULT DETENTION FACILITY
LIVING AREA SPACE EVALUATION
Board of State and Community Corrections
BSCC Code: 0706
FACILITY: Fresno County, West Annex Jail TYPE: II RC: 296
FIELD REPRESENTATIVE: Tim McWilliams DATE 10/30/24
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
Basement
B HLD1 Holding 2008 1 12 (12) 15’4”x10’x10’ 1 1 1
2- (112”) benches. (seating dimensions limit capacity to 12).
B HLD2 Holding 2008 1 11 (11) 15’4”x10’8”x10’ 1 1 1
1- (112”) / 1 (96”) benches. (seating dimensions limit capacity to 11)
B HLD3 Holding 2008 1 12 (12) 15’4”x10’8”x10’ 1 1 1
ADA accessible. 2- (112”) benches (seating dimensions limit capacity to 12).
First Floor – Used as a Day Reporting Center with no inmate housing. 9 visitation rooms + 14 video visitation units.
Second Floor
2A Pod
2A01- Double 2008 7 2 2 14 11’8” x 6’ x 8’10” 1 1 1
2A07
2A08- Double 2008 2 2 2 4 11’8” x 6’ x 8’10” 1 1 1
2A09
2A10 Double 2008 1 2 2 2 11’8’x 7’6”x 8’10” 1 1 1
2A11- Double 2008 4 2 2 8 11’8” x 6’ x 8’10” 1 1 1
2A14
Cell 2A10 is ADA-accessible cell. One shower area on each level. Dayroom contains 7 tables with 28 seats, plus ADA seating.
Exercise yard shared with Pod B. Cells 2A01-2A07 on upper level.
2B Pod
2B01- Double 2008 5 2 2 10 11’8”x6’x8’10” 1 1 1
2B05
2B06 Double 2008 1 2 2 2 11’8”x8’10”x8’10”
irregular shape
106 sf
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 1 - A360 LAS Adult-05.dot (8/05)
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
2B07- Double 2008 5 2 2 10 11’8 x 6” x 8’11 1 1 1
2B11 ½”
2B12 Double 2008 1 2 2 2 11’8”x 8’10”x 8’11 1 1 1
½” irregular
shape
Cell 2B12 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 12 seats, plus ADA seating. Sub-
Dayroom has 3 tables with 12 seats, plus ADA seating. Exercise yard shared with Pod A. Cells 2B1–2B5 on upper level.
2C Pod
2C01 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
2C02- Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
2C05
2C06 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
2C07- Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
2C10
Cell 2C06 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, ADA seating. Sub-
Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod D. Cells 2C1–2C5 are on upper level.
2D Pod
2D01- Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
2D04
2D05 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
2D06- Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
2D09
2D10 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
Cell 2D10 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, plus ADA seating.
Sub-Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod C. Cells 2D1-2D5 are on upper
level.
2E Pod
2E01 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
2E02- Double 2008 5 2 12 10 11’8”X6’X8’10” 1 1 1
2E06
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 2 - A360 LAS Adult-05.dot (8/05)
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
2E07 Double 2008 1 2 2 2 11’8”x8’10”x8’10” 1 1 1
irregular shape
2E08- Double 2008 5 2 12 10 11’8”X6’X8’10” 1 1 1
2E12
Cell 2E7 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 12 seats, plus ADA seating. Sub-
Dayroom has 3 tables with 12 Seats, plus ADA seating. Exercise yard shared with Pod F. Cells 2E1-2E6 on upper level.
2F Pod
2F01– Double 2008 7 2 2 14 11’8”x6’x8’10” 1 1 1
2F07
2F08-2F11 Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
2F12 Double 2008 1 2 2 2 11’8”x7’8”x8’10” 1 1 1
2F13-2F14 Double 2008 2 2 2 4 11’8”x6’x8’10” 1 1 1
Cell 2F12 is ADA-accessible cell. One shower on each level. Dayroom contains 7 tables with 28 seats, plus ADA seating.
Exercise yard shared with Pod E. Cells 2F1-2F07 on upper level.
Second Floor Holding
2 HLD1, Holding 2008 2 - 3 (6) 9’2”x7”3”X9’ 1 1 1
2 HLD2
ADA-accessible cells. 54” bench
Safety Cell Area Second Floor
2SC Safety 2008 1 - 1 (1) 8’1/2”x6’6
½”x8’10”
2OB Observatio 2008 1 - 1 (1) Irregular cell = 1 1 1
n 72.21 sq.ft.
Cell 2OB is ADA-accessible. ADA-accessible shower located between 2SC and 2OB. Elevated concrete pad in 2OB for bed.
2G Pod
2G01,2G2 Single 2008 2 1 1 2 11’8”X6’X9’6” 1 1 1
2G03 Single 2008 1 1 1 1 11’8”x7’8”X9’6” 1 1 1
Cell 2G03 is ADA-accessible cell. Dayroom has 1 table with 2 seats, plus ADA seating. Exercise area is accessed through
dayroom. One ADA-accessible shower in dayroom. Located next to 2F Pod.
2H Pod
2 H01 Single 2008 1 1 1 1 11’8”x7’8”X9’6” 1 1 1
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 3 - A360 LAS Adult-05.dot (8/05)
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
2 H02, Single 2008 2 1 1 2 11’8”X6’X9’6” 1 1 1
2 H03
Cell 2H01 is ADA-accessible cell. Dayroom has 1 table with 2 seats, plus ADA seating. Exercise area is accessed through
dayroom. One ADA-accessible shower in dayroom. Located next to 2A Pod.
Third Floor
3A Pod
3A01- Double 2008 7 2 2 14 11’7” x 6’ x 8’10” 1 1 1
3A07
3A08- Double 2008 2 2 2 4 11’8” x 6’ x 8’10” 1 1 1
3A09
3A10 Double 2008 1 2 2 2 11’8’x 7’7”x 8’10” 1 1 1
3A11- Double 2008 4 2 2 8 11’7” x 6’ x 8’10” 1 1
1
3A14
Cell 3A10 is ADA-accessible cell. One shower area on each level. Dayroom contains 7 tables with 28 seats, plus ADA seating.
Exercise yard shared with Pod 3B. Cells 3A01-3A07 on upper level.
3B Pod
3B01- Double 2008 5 2 2 10 11’7”x6’x8’10” 1 1 1
3B05
3B06 Double 2008 1 2 2 2 12’3”x8’8”x8’10”
irregular shape
106 sf
3B07- Double 2008 5 2 2 10 11’7 x 6” x 8’10” 1 1 1
3B11
3B12 Double 2008 1 2 2 2 12’3”x 8’8”x 8’10” 1 1 1
irregular shape
Cell 3B12 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 12 seats, plus ADA seating. Sub-
Dayroom has 3 tables with 12 seats, plus ADA seating. Exercise yard shared with Pod 3A. Cells 3B01-3B06 on upper level.
3C Pod
3C01 Double 2008 1 2 2 2 12’2”x8’8”x8’10” 1 1
1
irregular shape
3C02- Double 2008 4 2 2 8 11’8”X6’X8’10” 1 1 1
3C05
3C06 Double 2008 1 2 2 2 12’2”x8’8”x8’10” 1 1 1
irregular shape
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 4 - A360 LAS Adult-05.dot (8/05)
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
3C07- Double 2008 4 2 2 8 11’7”X6’X8’10” 1 1 1
3C10
Cell 3C06 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, ADA seating. Sub-
Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod 3D. Cells 3C1-3C5 are on upper level.
3D Pod
3D01- Double 2008 4 2 2 8 11’7”X6’X8’10” 1 1 1
3D04
3D05 Double 2008 1 2 2 2 12’2”x8’8”x8’10”
irregular shape
(108sf)
3D06- Double 2008 4 2 2 8 11’7”X6’X8’10” 1 1 1
3D09
3D10 Double 2008 1 2 2 2 12’2”x8’08”x8’10” 1 1 1
irregular shape
(108sf)
Cell 3D10 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, plus ADA seating.
Sub-Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod 3C. Cells 3D01-3D05 are on upper
level.
3E Pod
3E01 Double 2008 1 2 2 2 12’2”x8’8”x8’10” 1 1 1
irregular shape
3E02- Double 2008 5 2 2 10 11’8”X6’X8’10”
3E06
3E07 Double 2008 1 2 2 2 12’28”x8’08”x8’10 1 1 1
” irregular shape
3E08- Double 2008 5 2 2 10 11’8”X6’X8’10” 1 1 1
3E12
Cell 3E07 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, plus ADA seating.
Sub-Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod 3F. Cells 3E01-3E06 are on upper
level.
3F Pod
3F01-3F07 Double 2008 7 2 2 14 11’8”x6’x8’10” 1 1 1
3F13-3F14
3F08-3F11 Double 2008 4 2 2 8 11’7”X6’X8’10” 1 1 1
3F12 Double 2008 1 2 2 2 11’7”x7’8”x8’10” 1 1 1
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 5 - A360 LAS Adult-05.dot (8/05)
ROOMS EACH ROOM
Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES*
Location Type Standards Cell # Beds RC RC (L x W x H) T U W F S
s
Cell 3F12 is ADA-accessible cell. One shower on each level. Dayroom contains 3 tables with 10 seats, plus ADA seating.
Sub-Dayroom has 3 tables with 10 seats, plus ADA seating. Exercise yard shared with Pod 3E. Cells 3F01-3F07 are on upper
level.
Third Floor Holding
3 HLD1, Holding 2008 2 - 3 (6) 9’4”x7”4”X8’11” 1 1 1
3 HLD2
ADA-accessible cells. 54” bench
Third Floor Safety Cell Area
3SC Safety 2008 1 - 1 (1) 8’5”x6’4”x 8’10”
3OB Observatio 2008 1 - 1 (1) Irregular cell =
n 72.21 sf
Cell 3OB is ADA-accessible. ADA-accessible shower located between 3SC and 3OB. Elevated concrete pad in 3OB for bed.
3G Pod
3G01, Single 2008 2 1 1 2 11’8”X6’X9’6” 1 1 1
3G02
3G03 Single 2008 1 1 1 1 11’8”x7’7”X9’6” 1 1 1
Cell 3G03 is ADA-accessible cell. Dayroom has 1 table with 2 seats, plus ADA seating. Exercise area is accessed through
dayroom. One shower in dayroom. Located next to 3F Pod.
3H Pod
3H01 Single 2008 1 1 1 1 11’8”x7’7”X9’6” 1 1 1
3H02,3H0 Single 2008 2 1 1 2 11’8”X6’X9’6” 1 1 1
3
Cell 3H01 is ADA-accessible. Dayroom has 1 table with 2 seats, plus ADA seating. Exercise area is accessed through
dayroom. One shower in dayroom. Located next to 3A Pod.
*T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated
capacity. "+" indicates that capacity includes prorated air space from adjacent areas.
0706 Fresno West Annex LASE 23-24 - 6 - A360 LAS Adult-05.dot (8/05)