July 11, 2023 Dale Frisby Judicial Council of California 2860 Gateway Oaks Dr, Suite 400 Sacramento, CA 95833-4272 COUNTY OF IMPERIAL – EL CENTRO COURTHOUSE, BSCC PLAN REVIEW 025- 0917.01 Dear Mr. Frisby: On Monday, July 10, 2023, the Board of State and Community Corrections (BSCC) conducted the Pre-Opening Inspection of the new El Centro Courthouse located at 650 Wake Avenue, El Centro, California, for compliance with the applicable Minimum Standards for Local Detention Facilities as outlined in 2017’s Title 24, California Code of Regulations. The resulting inspection report is comprised of this letter and the attached documents including a Physical Plant Evaluation (PHY) outlining Title 24 requirements for the design and a Living Area Space Evaluation (LASE) that summarizes the facility’s configuration and rated capacity; the holding capacity of the facility is 73. During my inspection, I found the project met Title 24 requirements, and I found no areas of noncompliance. I have visited the construction site on several occasions and offered technical assistance to the construction team in resolving a compliance issue encountered during construction. I appreciate the attention and effort devoted to this project. Everyone involved supported the goal of constructing a safe and secure facility. Please contact me at (916) 621-4325 or by email at jill.farris@bscc.ca.gov if I can further assist you. Sincerely, JILL FARRIS Field Representative Facilities Standards and Operations Division Enclosures Cc: Fred Miramontes, Sheriff-Coroner Deepika Padam, Judicial Council Quality Compliance Manager ADULT DETENTION FACILITY LIVING AREA SPACE EVALUATION Board of State and Community Corrections BSCC Code: 0917 FACILITY: El Centro Courthouse TYPE: CH RC: (73) FIELD REPRESENTATIVE: Jill Farris DATE: 07/10/2023 ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S First Floor 5 Holding 2017 1 - (3) (3) 8’04”x 9’04”x 10’ 1 - 1 1 - Note: This is an irregularly shaped, ADA-accessible cell, with a 5’0” bench. 4 & 3 Holding 2017 2 - (5) (10) 7’6”x 9’06”x 10’ 1 - 1 1 - Note: These are irregularly shaped cells, each with a 7’06” bench. 2 Holding 2017 1 - (6) (6) 11’07”x 9’10”x 10’ 1 - 1 1 - Note: This is an irregularly shaped cell with a 9’11” bench. 8 Holding 2017 1 - (10) (10) 16’01”x 9’06”x 10’ 1 - 1 1 - Note: This is an irregularly shaped group cell, with a 16’ bench. 7 Holding 2017 1 - (10) (10) 16’03”x 9’04”x 10’ 1 - 1 1 - Note: This is an irregularly shaped group cell, with a 16’03” bench. 1 Holding 2017 1 - (9) (9) 13’11”x 9’07”x 10’ 1 - 1 1 - Note: This is an irregularly shaped group cell, with a 13’11” bench. 6 Holding 2017 1 - (5) (5) 9’07”x 8’x 10’ 1 - 1 1 - Note: This is an irregularly shaped cell, with an 8’ bench. Second Floor West Side 2 Holding 2017 1 - (3) (3) 7’06”x 11’01”x 10’ 1 - 1 1 - Note: This is an irregularly shaped, ADA-accessible cell, with a 5’0” bench. 1 Holding 2017 1 - (7) (7) 7’00”x 11’01’x 10’ 1 - 1 1 - Note: This is an irregularly shaped cell with two benches adjacent. One bench is 6’06” and the other is 5’06” =144” of bench space; however, the cell is approx. 77 sq ft. Second Floor East Side 4 Holding 2017 1 - (3) (3) 7’06”x 11’00”x 10’ 1 - 1 1 - *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 0917 Imperial El Centro Courthouse CH LASE 23-24 - 1 - A360 LAS Adult-05.dot (8/05) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S Note: This is an irregularly shaped, ADA-accessible cell, with a 5’0” bench. 3 Holding 2017 1 - (7) (7) 7’05”x 11’00”x 10’ 1 - 1 1 - Note: This is an irregularly shaped cell with two benches adjacent. One bench is 6’06” and the other is 5’06” =144” of bench space; however, the cell is approx. 77 sq ft. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 0917 Imperial El Centro Courthouse CH LASE 23-24 - 2 - A360 LAS Adult-05.dot (8/05) ADULT COURT AND TEMPORARY HOLDING FACILITIES PHYSICAL PLANT EVALUATION The Board of State and Community Corrections APPLICABLE TITLE 24 REGULATIONS: 2017 BSCC Code: 0917 FACILITY NAME: El Centro Courthouse FACILITY TYPE: CH 6/94: 2/99: 2001: 2005: 2008: 2010: ☐ ☐ ☐ ☐ ☐ ☐ APPLICABLE REGULATIONS (Check All That Apply): 2013: ☐ 2017: ☒ ☐ ☐ ☐ FIELD REPRESENTATIVE: Jill Farris DATE: July 10, 2023 TITLE 24 SECTION YES NO N/A COMMENTS The design of court holding and temporary holding facilities shall include the following required spaces from Sections 1231.2.2, 1231.2.19, 1231.2.20, 1231.2.21, 1231.2.22, 1231.2.24, and 1231.2.26. 1231.2.2 Temporary holding cell or room. A temporary holding cell or room shall: 1. Contain a minimum of 10 square feet (0.93 m2) ☒ ☐ ☐ of floor area per inmate; 2. Be limited to no more than 16 inmates; ☒ ☐ ☐ 3. Be no smaller than 40 square feet (3.7 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☒ ☐ ☐ more; 4. Contain seating to accommodate all inmates as required in Section 1231.3; ☒ ☐ ☐ 5. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☒ ☐ ☐ 6. Maximize visual supervision of inmates by staff; and ☒ ☐ ☐ 7. When located in a temporary holding facility, the cell or room shall be equipped with a bunk if inmates ☐ ☐ ☒ are to be held longer than 12 hours. 1231.2.19 Safety equipment storage. A secure area shall be provided for the storage of safety equipment such as fire extinguishers, self-contained ☒ ☐ ☐ breathing apparatus, wire and barcutters, emergency lights, etc.. 1231.2.20 Janitors’ closet. In Type II facilities, at least one securely lockable janitors’ closet with sufficient area for the storage of ☒ ☐ ☐ cleaning implements and supplies must be provided within the security areas of the facility A mop sink shall also be available within the security area of the facility. In court holding, temporary holding, Types I, III and IV facilities, the closet need not be in the security area. ☒ ☐ ☐ 0917 Imperial El Centro Courthouse CH PHY 23-24 - 1 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.21 Storage rooms. One or more storage rooms shall be provided to accommodate a minimum of 80 cubic feet (2.3 m3) of storage area per inmate for inmate clothing and personal property, institutional clothing, bedding and ☒ ☐ ☐ supplies. Court holding, temporary holding and Type I facilities may be excluded from the storage space requirement for personal and institutional clothing unless clothing is issued. 1231.2.22 Audio monitoring system. In court holding, temporary holding, Type I, Type II and Type II facilities there shall be an inmate- or sound- actuated audio monitoring system in temporary holding cells or rooms, temporary staging cells or rooms, sobering cells, safety cells, single and double ☒ ☐ ☐ occupancy cells, dormitories, dayrooms, exercise areas and correctional program/multipurpose space, which is capable of alerting personnel who can respond immediately. 1231.2.24 Emergency power. There shall be a source of emergency power in all detention facilities capable of providing minimal lighting in all housing units, activities areas, corridors, stairs and ☒ ☐ ☐ central control points, and to maintain fire and life safety, security, communications and alarm systems. Such an emergency power source shall conform to the requirements specified in Title 24, Part 3, Article 700, California Electrical Code, California Code of ☒ ☐ ☐ Regulations. 1231.2.26 Attorney interview space. All facilities except Type IV facilities shall include attorney interview areas which provide for confidential ☒ ☐ ☐ consultation with inmates. 1231.3.1 Toilets/urinals. In temporary holding cells and temporary staging cells toilets/urinals must be provided in a ratio to inmates of ☒ ☐ ☐ 1:16. One urinal or 2 feet (610 mm) of urinal trough may be substituted for each toilet up to one third of the total number of toilets required, except in those facilities or ☒ ☐ ☐ portions thereof used for females. Toilet areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.2 Wash basins. In temporary holding cells and temporary staging cells, wash basins must be provided in a ratio to inmates of ☒ ☐ ☐ 1:16. Wash basins must be provided with hot and cold or tempered water. ☒ ☐ ☐ Two feet (610 mm) of wash basin trough may be substituted for each basin required. ☐ ☐ ☒ 0917 Imperial El Centro Courthouse CH PHY 23-24 - 2 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.3.3 Drinking fountains. There must be a minimum of one drinking fountain in every single-occupancy cell, double-occupancy cell, dormitory, temporary holding cell, temporary staging ☒ ☐ ☐ cell, sobering cell, and be accessible to the occupants of day rooms and exercise areas. Additional drinking fountains shall be located in other areas of the facility so that drinking water will be ☒ ☐ ☐ available to inmates and staff. Such drinking fountains must meet the following minimum health requirements: 1. The drinking fountain bubbler shall be on an ☒ ☐ ☐ angle which prevents waste water from flowing over the drinking fountain bubbler. 2. Water flow shall be actuated by mechanical means. ☒ ☐ ☐ 1231.3.6 Lighting. Lighting in housing units, dayrooms and activity areas must be sufficient to permit easy reading by a person with normal vision, and shall not be less than 20 ☒ ☐ ☐ footcandles (215.2 lux) at desk level and in the grooming area. Lighting shall be centrally controlled and/or occupant controlled in housing cells or rooms. ☒ ☐ ☐ Night lighting in these areas shall be sufficient to give good visibility for purposes of supervision ☒ ☐ ☐ In minimum-security areas, lighting may be supplied by ordinary lighting fixtures, and in areas of higher ☒ ☐ ☐ security, light fixtures must be of secure design. 1231.3.10 Seating. In temporary holding and temporary staging cells, ☒ ☐ ☐ seating must be securely fixed to the floor and/or wall. When bench seating is used, 18 inches (457 mm) of bench is seating for one person. ☒ ☐ ☐ 1231.3.12 Weapons locker. A secure weapons locker shall be located outside the ☒ ☐ ☐ security perimeter of the facility Such weapons lockers shall be equipped with individual compartments, each with an individual locking device. ☒ ☐ ☐ Weapons lockers are required in temporary and court holding facilities and in all facilities of higher than ☒ ☐ ☐ minimum security. Design Requirements (102(c)6) Design requirements as specified in Title 24, Part 1, 102(c)6 are met. (See regulation for specific requirements. Note areas of non-compliance that are ☒ ☐ ☐ applicable to the facility type and construction date in the "comments" section.) 0917 Imperial El Centro Courthouse CH PHY 23-24 - 3 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19)