All bodies  ›  Board of State and Community Corrections  ›  Stanislaus County Sheriff's Department (2023-2024 inspection cycle)

BSCC

Stanislaus County Sheriff's Department (2023-2024 inspection cycle)

Board of State and Community Corrections · inspection-5730p-2023-2024 · Facility inspection · 2024-05-10 · Stanislaus County Sheriff's Department

Read the report at Stanislaus County Sheriff's Department ↗

May 10, 2024 Jeff Dirkse, Sheriff Stanislaus County Sheriff’s Department 250 E. Hackett Road Modesto, CA 95358 2023-2024 TARGETED INSPECTION, PENAL CODE SECTION 6031, WELFARE & INSTITUTIONS CODE SECTION 209, STANISLAUS COUNTY DETENTION FACILITIES Dear Sheriff Dirkse: The 2023-2024 Targeted Inspection of the Stanislaus County Sheriff's Department detention facilities have been completed. The following facilities were inspected on Tuesday, April 23, 2024: FACILITY NAME BSCC # FACILITY TYPE Stanislaus County Public Safety 5730 II Center East/West Facilities Public Safety Center Units 1 & 2 5743 II REACT Center 5735 II These inspections were conducted pursuant to Penal Code Section 6031 to determine compliance with the Minimum Standards for Local Detention Facilities as outlined in Titles 15 and 24, California Code of Regulations. In addition, Board of State and Community Corrections (BSCC) staff conducted compliance monitoring pursuant to Welfare and Institutions Code Section 209(f). In addition to the inspection(s) by the BSCC, inspections are also required annually by the County Health Officer and biennially by the State Fire Marshal or an authorized representative (Health and Safety Code Sections 101045 and 13146.1). The results of those inspections are considered a part of this report. INSPECTION RESULTS We identified no items of noncompliance with Title 15 Minimum Standards. Refer to the attached Title 15 Procedures Checklist for detailed information. No items of noncompliance were identified with Title 24 Minimum Standards. Refer to the Physical Plant Evaluation (PHY) and Living Area Space Evaluation (LASE) attachments for information related to Rated Capacity. * * * Jeff Dirkse Sheriff Page 2 Please email me at tim.mcwilliams@bscc.ca.gov or call (916) 956-1559 if you have any questions. Sincerely, TIM MCWILLIAMS Field Representative Facilities Standards and Operations Division Enclosures Cc: Presiding Judge, Stanislaus County Superior Court* Chair, Grand Jury, Stanislaus County* Chair, Board of Supervisors, Stanislaus County* County Administrator, Stanislaus County* Richard Ballard, Sergeant, Stanislaus County Sheriff’s Department (email copy) Scott Houston, Captain, Stanislaus County Sheriff's Department (email copy) *Copies of the inspection are available upon request or online at www.bscc.ca.gov. 5730+ Stanislaus County Sheriff’s Department II Targeted LTR 23-24 TYPE II AND III FACILITIES Board of State and Community Corrections PROCEDURES1 BSCC Code: 5730 FACILITY NAME: Stanislaus Public Safety Center East/West Facility FACILITY TYPE: II PERSON(S) INTERVIEWED: Lt. Marquez, Sgt. Baez, Sgt. Gutierrez, Sgt. Ballard, Dep. Delgadillo, Dep. Flores, Dep. Castillo FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS 1027.5 SAFETY CHECKS SCSDPPMADD 9-01.01 Security Inspections SCSDPPMADD 9-01.06 Electronic The facility administrator shall develop and implement Documentation System policy and procedures for conducting safety checks that include, but are not limited to, the following: ☒ ☐ ☐ (a) Safety checks will determine the safety and well- being of individuals and shall be conducted at least hourly through direct visual observation of all people held and housed in the facility. (b) There shall be no more than a 60-minute lapse ☒ ☐ ☐ between safety checks. (c) Safety checks for people in sobering cells, safety cells, and restraints shall occur more frequently as ☒ ☐ ☐ outlined in section 1055, section 1056, and section 1058 of these regulations. (d) Safety checks shall occur at random or varied ☒ ☐ ☐ intervals. (e) There shall be a written plan that includes the documentation of all safety checks. Documentation shall include: ☒ ☐ ☐ (1) the actual time at which each individual safety check occurred; (2) the location where each individual safety check occurred, such as a cell, module, or dormitory ☒ ☐ ☐ number; and, (3) Initials or employee identification number of staff ☒ ☐ ☐ who completed the safety check(s). 1 This document is intended for use as a tool during the targeted inspection process; this worksheet may not contain each Title 15 regulation that is required. Additionally, many regulations on this worksheet are SUMMARIES of the regulation; the text on this worksheet may not contain the entire text of the actual regulation. Please refer to the complete California Code of Regulations, Title 15, Minimum Standards for Local Facilities, Division 1, Chapter 1, Subchapter 4 for the complete list and text of regulations. 5730 Stanislaus Public Safety Center East/West Facility II PRO 23-24 Page 1 of 5 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (f) A documented process by which safety checks are An electronic safety check system is utilized. reviewed at regular defined intervals by a supervisor or The system identifies safety checks that are facility manager, including methods of mitigating over 60 minutes and those employees that patterns of inconsistent documentation, or untimely have late safety checks must write a memo completion of, safety checks. identifying why the check was late and that they understand the agency policy. All safety ☒ ☐ ☐ checks and memos are reviewed by a supervisor. Approximately three months of safety check documentation was requested for review for this inspection. The review of documentation identified that safety checks are being completed within the time identified in this regulation and at random times. 1032 FIRE SUPPRESSION PREPLANNING SCSDPPMADD 10-01.01 Fire Suppression Planning Pursuant to Penal Code Section 6031.1(b), the facility administrator shall consult with the local fire department ☒ ☐ ☐ having jurisdiction over the facility, with the State Fire Marshal, or both, in developing a plan for fire suppression which shall include, but not be limited to: (a) a fire suppression pre-plan developed with the local fire department to be included as part of the policy and ☒ ☐ ☐ procedures manual (Title 15, California Code of Regulations Section 1029); (b) monthly fire prevention inspections by facility staff ☒ ☐ ☐ with two-year retention of the inspection record; (c) fire prevention inspections as required by Health and Safety Code Section 13146.1(a) and (b) which requires ☒ ☐ ☐ inspections at least once every two years; (d) an evacuation plan; and, ☒ ☐ ☐ (e) a plan for the emergency housing of incarcerated ☒ ☐ ☐ people in the case of fire. 1056 USE OF SOBERING CELL SCSDPPMADD 2-05.01 Sobering Cell The sobering cell described in Title 24, Part 2, Section ☒ ☐ ☐ 1231.2.4, shall be used for temporary holding of incarcerated people who are a threat to their own safety Only the East Unit has Sobering Cells. The or the safety of others due to their state of intoxication. West does not have any. A person shall be removed from the sobering cell as soon as they are able to continue the admission process ☒ ☐ ☐ or are no longer a risk to themselves or others. In no case shall a person remain in a sobering cell over Medical checks each person in the Sobering six hours without an evaluation by medical or custody Cell at placement, then within every six hours. staff to determine whether the person has an urgent ☒ ☐ ☐ Once the incarcerated person can care for medical problem, pursuant to section 1213 of these themselves, they move them out of the regulations. sobering cell. At 12 hours from the time of placement, all persons must ☒ ☐ ☐ receive an evaluation by responsible health care staff. 5730 Stanislaus Public Safety Center East/West Facility II PRO 23-24 Page 2 of 5 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS Intermittent direct visual observation of people held in Two months of sobering cell placements were the sobering cell shall be conducted no less than every requested for this inspection. Department half hour. Such observation shall be documented. policy states that checks are to be made every 15 minutes. A review of the documentation found that observation checks are made ☒ ☐ ☐ approximately every 15 minutes. When a check is not conducted within 15 minutes, a memorandum from the staff member working is required. Each placement in the sobering cell is reviewed by a supervisor and an audit is completed. 1058 USE OF RESTRAINT DEVICES SCSDPPMADD 09-06.04 Restraint Devices SCSDPPMADD 09-06.05 Restraint Chair The facility administrator, in cooperation with the SCSDPPMADD 09-06.06 Observation responsible physician, shall develop and implement Room/Restraint Bed written policies and procedures for the use of restraint SCSDPPMADD 09-06.07 The WRAP devices. Restraint devices include any devices which Restraint immobilize extremities or prevent the incarcerated ☒ ☐ ☐ person from being ambulatory. The provisions of this The West and East have restraint chairs. The section do not apply to the use of handcuffs, shackles, East has a restraint bed, which was not used or other restraint devices when used to restrain during this inspection review. There was one incarcerated people for security reasons. The facility instance of restraint chair usage during this manager may delegate authority to place an inspection time frame. incarcerated person in restraints to responsible health care staff. (a) The policy shall address the following areas: ☒ ☐ ☐ (1) acceptable restraint devices; (2) signs or symptoms which should result in immediate medical/mental health referral; ☒ ☐ ☐ availability of cardiopulmonary resuscitation equipment; (3) protective housing of restrained persons; ☒ ☐ ☐ (4) provision for hydration and sanitation needs; and, ☒ ☐ ☐ (5) exercising of extremities. ☒ ☐ ☐ (b) Policy shall also include, but not be limited to, the following requirements: ☒ ☐ ☐ (1) In no case shall restraints be used for punishment or as a substitute for treatment. (2) Restraint devices shall only be used on incarcerated people who display behavior which ☒ ☐ ☐ results in the destruction of property or reveal an intent to cause physical harm to self or others. (3) Restraint devices should be used only when less restrictive alternatives, including verbal de- ☒ ☐ ☐ escalation techniques, have been attempted and are deemed ineffective. (4) An incarcerated person shall be placed in restraints only with the approval of the facility manager, the facility watch commander, or ☒ ☐ ☐ responsible health care staff; continued retention shall be reviewed a minimum of every hour. 5730 Stanislaus Public Safety Center East/West Facility II PRO 23-24 Page 3 of 5 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (5) Continuous direct visual observation shall be ☒ ☐ ☐ maintained until a medical opinion can be obtained. (6) A medical opinion on placement and retention shall be secured within one hour from the time of ☒ ☐ ☐ placement. (7) A medical assessment shall be completed within ☒ ☐ ☐ four hours of placement. (8) Continuous direct visual observation shall be Placement for those in the restraint chair is conducted at least twice every 30 minutes to ensure normally a safety cell and housed alone. that the restraints are properly employed, and to Direct visual observations are noted in the ensure the safety and well-being of the incarcerated agency's electronic security verification person. Such observation shall be documented. ☒ ☐ ☐ system. The entries identify observable While in restraint devices all incarcerated persons factors related to the incarcerated person’s shall be housed alone or in a specified housing area behavior. Supervisor and Medical reviews which makes provisions to protect the person from are also included. Observations are abuse. conducted twice every 30 minutes. (9) If the facility manager, or designee, in consultation with responsible health care staff determines that an incarcerated person cannot be ☒ ☐ ☐ safely removed from restraints after eight hours, the person shall be taken to a medical facility for further evaluation. (10) Where applicable, the facility manager shall use the restraint device manufacturer’s recommended ☒ ☐ ☐ maximum time limits for placement. (11) All events and information related to the placement in restraints shall be documented and shall be video recorded unless exigent circumstances prevent staff from doing so. The ☒ ☐ ☐ documentation shall include: the reason for placement; person authorizing placement; names of staff involved in the placement; injuries sustained; and the duration of placement. 1065 EXERCISE AND OUT OF CELL TIME SCSDPPMADD 04-01.25 Yard Deputy (a) The facility administrator of a Type II or III facility shall Housing movement logs for three consecutive develop written policies and procedures for a minimum months were requested for this inspection. of 10 hours of out of cell time distributed over a period of For persons housed in administrative seven days to include: separation units, each day was recorded as either the time the person was in the recreation area, when the cell did not have an ☒ ☐ ☐ occupant, and times of refusal were noted. When in a housing area for an entire week, more than 10 hours of exercise and recreation were provided. In other areas, schedules are used to inform incarcerated persons of when they can use the exercise yard and the dayrooms. These are well above the 10-hour out-of-cell time. (1) an opportunity for three hours of exercise and ☒ ☐ ☐ (2) an opportunity for seven hours of recreation. ☒ ☐ ☐ 5730 Stanislaus Public Safety Center East/West Facility II PRO 23-24 Page 4 of 5 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS Policies shall include reasonable and necessary ☒ ☐ ☐ procedures to ensure safety and security. 5730 Stanislaus Public Safety Center East/West Facility II PRO 23-24 Page 5 of 5 A353 Type II & III Targeted PRO eff 01.2024 ADULT DETENTION FACILITY LIVING AREA SPACE EVALUATION Board of State and Community Corrections BSCC Code: 5730 FACILITY: Stanislaus Public Safety Center East/West Facility TYPE: II RC: 1,014 FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S East and West facilities operate separately. All bookings occur at the East facility. Pre-Booking R113 Holding 2010 1 (4) (4) 9' x 6'9" 1 1 1 Bench seat 6’9”. Seating limits capacity. BOOKING/INTAKE (AB 900 Project) Note: There is also an open waiting area for those who can proceed through the booking process. R110 Sobering 2010 1 (5) (5) 16'4" x 7'3" 1 1 1 R111 Sobering 2010 1 (5) (5) 9'7" x 10'6" 1 1 1 R112 Sobering 2010 1 (8) (8) 16'4" x 10'5" 1 1 1 ADA cell. R107 Sobering 2010 1 (6) (6) 12' x 10'5" 1 1 1 R108 Sobering 2010 1 (6) (6) 12' x 10'5" 1 1 1 R109 Sobering 2010 1 (4) (4) 12' x 7'5" 1 1 1 R121 Holding 2010 1 (8) (8) 9'9" x 10'2" 1 1 1 Note: Bench 10'2" (6) and 4'2" (2); capacity based on seating. (20-22) ADA cell. R106 Safety 2010 1 (1) (1) 10' x 6'8" 1 R101- Safety 2010 5 (5) (5) 10' x 6'10" 1 R105 R120 Holding 2010 1 (6) (6) 9'9" x 10'4" 1 1 1 Note: Bench 10'4"; capacity based on seating. R119 Holding 2010 1 (4) (4) 10'1" x 6'8" 1 1 1 Note: Bench 6'8"; capacity based on seating. R118 Holding 2010 1 (4) (4) 10'1" x 6'10" 1 1 1 Note: Bench 6'10"; capacity based on seating. R117 Holding 2010 1 (4) (4) 10'1" x 6'10" 1 1 1 Note: Bench 6'10"; capacity based on seating. R114- Holding 2010 3 (4) (12) 10' x 6'10" 1 1 1 R116 Note: Bench 6'10"; capacity based on seating. R122- Holding 2010 4 (5) (20) 13'6" x 7'1" 1 1 1 R125 Note: Bench 8'; capacity based on seating. R126 Holding 2010 1 (13) (13) 13'6" x 13'4" 1 1 1 Note: Bench 13'6"+6'1"; capacity based on seating. (20-22) ADA cell. R127 Holding 2010 1 (9) (9) 13'6" x 7'1" 1 1 1 Note: Bench 13'6"+6'1"; capacity based on square footage of cell. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 1 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S R128 Holding 2010 1 (5) (5) 9'11" x 7'6" 1 1 1 Note: Bench 7'6"; capacity based on seating. R129 Holding 2010 1 (3) (3) 9'11" x 8'1" 1 1 1 Note” Bench 4'7"; capacity based on seating. (20-22) ADA cell. R135- Atty 2010 5 R139 (2024) Attorney visitation booths, R135 used as storage only. Release R130 Holding 2010 1 (4) (4) 6'9" x 8'9" 1 1 1 Note: Bench 6'9"; capacity based on seating. (20-22) ADA cell. R131 Holding 2010 1 (4) (4) 6'4" x 9'7" 1 1 1 Note: Bench 6'; capacity based on seating. UNIT B-Contains three separate housing areas; the main control center for the facility is also inside this wing/building. B101-102 Safety 1988 2 (1) (2) 9.8’x5.2’x8.1’ 1 B103-113 Single 1988 24 1 24 24 11.9’x6.5’x8.1’ 1 1 1 2 201-213 Note: This unit has lower and mezzanine levels; cells 103-113 are on the lower level and 201-213 are on the upper or mezzanine level. Dayroom approximately 2010 sq. ft. 2016-2018 inspection cycle – 2/7/18, these beds have changed from the Mental Health Unit to a High Risk/Walk Alone unit, changing these beds from non-rated to rated beds. The rated capacity of this unit is now 24. (2024) Security enclosure located in the center of dayroom. B114-123, Double 1988 20 2 2 40 11.9’x6.5’x8.1’ 1 1 1 2 214-223 Note: 10x4 (tables/seats). Cells 114-123 on the lower level; 214-223 on the mezzanine. 20 cells were doubled in 1999 with VOI/TIS funds. Dayroom approx. 1191 sq. ft. supports RC of 34. Alternate means of compliance is ongoing for 40 inmates. B124 – Single 1988 12 1 1 12 11.9’x6.5’x8.1’ 1 1 1 B135 B224 - Double 1988 14 2 2 28 11.9’x6.5’x8.1’ 1 1 1 2 B236 Note: 10x4 (tables/seats). Cell 124 is handicap accessible. Cells 124-135 on the lower level; 224-236 on the mezzanine. Dayroom approx. 2010 sq. ft. Unit C – Clinic C334 Holding 2010 1 (7) (7) 13'2" x 8'10" 1 1 1 Note: Bench 8' and 3’ L-shape; capacity based on seating. (20-22) ADA cell. The clinic also has an open waiting area. C333 Holding 2010 1 (7) (7) 13'2" x 8'11" 1 1 1 Note: Bench 7'6" and 3’ L-shape; capacity based on seating. (20-22) ADA cell. VIDEO ARRAIGNMENT WEST 0B This area was previously the booking and reception area. It has been renovated into a video courtroom. Inmates are escorted to this area and not placed in any cells. Since this was a non-rated area, the RC is not affected. UNIT D 1B 101, 112, 201, 202, Single 1988 26 1 1 26 11.9’x6. 5’x8. 1’ 1 1 1 213-234 102-111, 113-122, Double 1988 30 2 2 60 11.9’x6. 5’8. 1’ 1 1 7 203-212 Note: 17x4 (tables/seats), 8x6 (tables/seats). Three cluster sitting areas with 12 seats each. Cells 101-122 on the lower level; 201-234 on the mezzanine. Dayroom 4,780 sq. ft. UNIT E 2B *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 2 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S 101, 112, 201, 202, Single 1988 26 1 1 26 11.9’x6. 5’8. 1’ 1 1 1 213-234 102-111, 113-122, Double 1988 30 2 2 60 11.9’x6. 5x8.1’ 1 1 1 7 203-212 Note: 17x4 (tables/seats), 8x6 (tables/seats). Three cluster sitting areas with 12 seats each. Cells 101-122 on the lower level; 201-234 on the mezzanine. Dayroom approx. 5100 sq. ft. (23-24) E-101 is an ADA cell. UNIT F 3B 101, 112, 201, 202, Single 1988 26 1 1 26 11.9’x6. 5’x8. 1’ 1 1 1 213-234 102-111, 113-122, Double 1988 30 2 2 60 11.9’x6. 5’x8. 1’ 1 1 1 7 203-212 Note: 18x4 (tables/seats), 8x6 (tables/seats). Three cluster sitting areas, two with 11 seats each and one with 10 seats. Cells 101-122 on the lower level, 201-234 on the mezzanine. Dayroom approx. 5100 sq. ft. UNIT G 4B 101, 112, 201, 202, Single 1988 26 1 1 26 11.9’x6/5’x8. 1’ 1 1 1 213-234 102-111, 113-122, Double 1988 30 2 2 60 11.9’x6. 5’x8. 1’ 1 1 1 7 203-212 Note: 17x4 (tables/seats), 8x6 (tables/seats). Three cluster sitting areas, two with 12 seats each and one with 10 seats. Cells 101-122 on the lower level; 201-234 on the mezzanine. Dayroom approx. 5100 sq. ft. Unit H – Medical Sheltered Housing H101 Single 2010 1 1 (1) (1) 14'5" x 9'5" 1 1 1 Note: Tear away curtain H102 Single 2010 1 1 (1) (1) 14'5" x 12'6" 1 1 1 1 Note: Negative pressure room; (20-22) ADA cell. (23-24) A shower is located inside the cell. H103 Single 2010 1 1 (1) (1) 14'5" x 9'6" 1 1 1 1 Note: Negative pressure room; (23-24) A shower is located inside the cell. H104- Single 2010 2 1 (2) (2) 14'5" x 9'6" 1 1 1 H105 H106 Single 2010 1 1 (1) (1) 14'1" x 12'2" 1 1 1 Note: (20-22) ADA cell. H107- Single 2010 2 1 (1) (2) 14'1" x 9'6" 1 1 1 H108 H109 Single 2010 1 1 (1) (1) 14'1" x 12'3" 1 1 1 Note: (20-22) ADA cell. H110 Single 2010 1 1 (1) (1) 14'1" x 9'4" 1 1 1 H111 Single 2010 1 1 (1) (1) 13'2" x 13'2" 1 1 1 Note: (20-22) ADA cell. H112- Single 2010 4 1 (4) (4) 14’1”x9’4” 1 1 1 H115 H116 2010 1 1 NR 9’x11’ (20-22) This room houses a restraint bed. (23-24) It is rarely used (once in 5 years) and is not rated. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 3 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S UNIT I 101, 112, 201, 202, Single 1988 26 1 1 26 11.9’x6. 5’x8. 1’ 1 1 1 213-234 102-111 113-122 Double 1988 30 2 2 60 11.9’x6. 5’x8. 1’ 1 1 1 7 203-212 Note: 17 x 4 (tables/seats), 8x6 (tables/seats) Three cluster sitting areas, two with 12 seats each and one with 10 seats. Cells 101-122 on the lower level; 201-234 on the mezzanine. Dayroom approx. 5100 sq. ft. Unit K1 – Housing K703 Holding 2010 1 (4) 16'7" x 6'7" 1 1 1 Note: Bench 6'; seating limits capacity. K101 Double 2010 1 2 2 2 13'8" x 9' 1 1 1 Note: ADA cell; K102-K120 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Approximately 2,088 square feet of dayroom; 5 x 38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit K2 – Housing K201 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq. ft) Note: ADA cell; K202- K220 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit K3 – Housing K301 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq. ft) Note: ADA cell. K302- K320 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit K4 – Housing K401 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq. ft) Note: ADA cell. K402- K420 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit K5 – Housing K501 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq. ft) Note: ADA cell; K502- K520 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 4 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S Unit K6 – Housing K601 Double 2010 1 2 2 2 13'8" x 9' 1 1 1 Note: ADA cell. K602-K620 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L1 – Housing L703 Holding 2010 1 (4) 16'7" x 6'5" 1 1 1 Note: Bench 6'; seating limits capacity. (20-22) ADA cell. L101 Double 2010 1 2 2 2 13'8" x 9' 1 1 1 Note: ADA cell L102-L120 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L2 – Housing L201 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq.ft.) Note: ADA cell. L202- L220 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L3 – Housing L301 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq.ft.) Note: ADA cell. L302- L320 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L4 – Housing L401 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq.ft.) Note: ADA cell L402- L420 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L5 – Housing L501 Double 2010 1 2 2 2 Irregular shape 1 1 1 (70+ sq.ft) Note: ADA cell L502- L520 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit L6 – Housing L601 Double 2010 1 2 2 2 13'8" x 9' 1 1 1 *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 5 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S Note: ADA cell. L602-L620 Double 2010 19 2 2 38 13'8" x 6'2" 1 1 1 Note: Dayroom approximately 2,088 square feet; 5x38 (tables/seats -two spaces are open for wheelchair access). Two showers are available in the dayroom. Unit M1 – Medical/Mental Health Housing M101 Safety 2010 1 (1) 8' x 6'7" M102 Safety 2010 1 (1) 8'3" x 6'6" M103 Safety 2010 1 (1) 8'3" x 6'9" M104 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell M105- Single 2010 7 1 1 (7) 13'8" x 6'2" 1 1 1 M111 M112 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. Note: Dayroom approximately 1,790 square feet; 4x14 (tables/seats -two spaces are open for wheelchair access). One shower is available in the module. Unit M2 – Medical/Mental Health Housing M201 1 1 1 (1) Irregular shape 1 1 1 Single 2010 (approx. 135 sq. ft) Note: Negative pressure room. (23-24) Not used as a negative pressure room, inmates use the shower in the dayroom. M202 Single 2010 1 1 1 (1) 11'6" x 6'2" 1 1 1 Note: Negative pressure room. Shares anteroom with M201. (23-24) Not used as a negative pressure room, inmates use the shower in the dayroom. M203- Single 2010 8 1 1 (7) 13'8" x 6'2" 1 1 1 M209 M210 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. Note: Dayroom approximately 1,790 square feet; 4x14 (tables/seats - two spaces are open for wheelchair access). One shower is available in the module. Unit M3 – Medical/Mental Health Housing M301- Single 2010 7 1 1 (7) 13'8" x 6'2" 1 1 1 M307 M308 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. Note: Dayroom Approximately 1,625 square feet; 4x14 (tables/seats - two spaces are open for wheelchair access). One shower is available in the module. Unit M4 – Medical/Mental Health Housing M401 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. M402- Single 2010 8 1 1 (8) 13'8" x 6'2" 1 1 1 M409 M410 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: Dayroom approximately 1,625 square feet; 4x14 (tables/seats - two spaces are open for wheelchair access). One shower is available in the module. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 6 - A360 LAS Adult.dot (03/01) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S Unit M5 – Medical/Mental Health Housing M501 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. M502- Single 2010 7 1 1 (7) 13'8" x 6'2" 1 1 1 M508 M509 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: Dayroom approximately 1,790 square feet; 4 x 14 (tables/seats - two spaces are open for wheelchair access). One shower is available in the module. Unit M6 – Medical/Mental Health Housing (JBCT) M601 Single 2010 1 1 1 (1) 13'8" x 7'10" 1 1 1 Note: ADA cell. M602- Double 2010 6 2 2 (12) 13'8" x 6'2" 1 1 1 M607 M608- Single 2010 4 1 1 (4) 13'8" x 7'10" 1 1 1 M611 Note: Dayroom approximately 1,790 square feet; 4x14 (tables/seats -two spaces are open for wheelchair access). One shower is available in the module. H818 Video 2010 1 0 (18) 17’ X 14’ 1 1 (20-22) Originally used as storage. Changed into video arraignment due to COVID-19. 6’ concrete bench limits capacity. A separate restroom is available inside the holding area. Temporary staging criteria are used to determine capacity along with bench space. M819 Video 2010 1 0 (6) 7.6’ X 14’ 1 1 (20-22) Originally used as storage. Changed into video arraignment due to COVID-19. U-shaped concrete bench (8.6’ X 11’ X 8.6’). No fixtures in the holding area. Temporary staging criteria are used to determine capacity along with bench space. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit; if "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5730 Stanislaus Public Safety Center East/West Facility II LASE 23-24 - 7 - A360 LAS Adult.dot (03/01) ADULT TYPE I, II, III AND IV FACILITIES PHYSICAL PLANT EVALUATION The Board of State and Community Corrections APPLICABLE TITLE 24 REGULATIONS: 6/94; 2/99; 2001; 2005; 2008; 2010, 2013, 2017 BSCC Code: 5730 FACILITY NAME: Stanislaus Public Safety Center East/West Facility FACILITY TYPE: II 6/94: 2/99: 2001: 2005: 2008: 2010: ☐ ☐ ☐ ☒ ☐ ☐ APPLICABLE REGULATIONS (Check All That Apply): 2013: ☐ 2017: ☐ 5/88 ☐ ☐ ☐ ☒ FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.1 Reception and booking. Facilities where booking and housing occur shall have the following space and equipment: ☒ ☐ ☐ 1. Weapons locker as specified in Section 1231.3.12. 2. A cell or room for the confinement of inmates pending their booking, complying with Section ☒ ☐ ☐ 1231.2.2. 3. A sobering cell as described in Section 1231.2.4 if intoxicated, inmates who may pose a danger to ☒ ☐ ☐ themselves or others are held. For those facilities that accept male and female intoxicated inmates two sobering cells shall be ☒ ☐ ☐ provided. 4. Access to a shower within the secure portion of the facility. ☒ ☐ ☐ 5. Provide access to a secure vault or storage space for inmate valuables. ☒ ☐ ☐ 1231.2.2 Temporary holding cell or room. A temporary holding cell or room shall: 1. Contain a minimum of 10 square feet (0.93 m2) ☒ ☐ ☐ of floor area per inmate; 2. Be limited to no more than 16 inmates; ☒ ☐ ☐ 3. Be no smaller than 40 square feet (3.7 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☒ ☐ ☐ more; 4. Contain seating to accommodate all inmates as required in Section 1231.3; ☒ ☐ ☐ 5. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☒ ☐ ☐ 6. Maximize visual supervision of inmates by staff; and ☒ ☐ ☐ 7. When located in a temporary holding facility, the cell or room shall be equipped with a bunk if inmates ☒ ☐ ☐ are to be held longer than 12 hours. 1231.2.3 Temporary staging cell or room. No temporary staging cells at this facility. A temporary staging cell or room shall: 1. Be constructed for the purpose of holding inmates who have been classified and segregated ☐ ☐ ☒ in accordance with Sections 1050 and 1053 of Title 15, Division 1, California Code of Regulations. 2. Be limited to holding inmates up to four hours. ☐ ☐ ☒ 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 1 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 3. Be limited to no more than 80 inmates. ☐ ☐ ☒ 4. Contain a minimum of 10 square feet (0.93 m2) of floor area per inmate and a clear ceiling height of ☐ ☐ ☒ 8 feet (2438 mm) or more. 5. Be no smaller than 160 square feet (14.9 m2). ☐ ☐ ☒ 6. Contain seating to accommodate all inmates as required in Section 1231.3. ☐ ☐ ☒ 7. Contain toilet, wash basin and drinking fountain as specified in Section 1231.3. ☐ ☐ ☒ 8. Maximize visual supervision of inmates by staff. ☐ ☐ ☒ 1231.2.4 Sobering cell. The East facility is the intake facility and A sobering cell shall: contains sobering cells. The West facility 1. Contain a minimum of 20 square feet (1.9 m2) of ☒ ☐ ☐ does not have sobering cells. floor area per inmate; 2. Be limited to eight inmates; ☒ ☐ ☐ 3. Be no smaller than 60 square feet (5.6 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☒ ☐ ☐ more; 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☒ ☐ ☐ 5. Have padded partitions located next to toilet fixture in such a manner that they provide support ☒ ☐ ☐ to the user; 6. Maximize visual supervision of inmates by staff; ☒ ☐ ☐ 7. Be padded on the floor as specified in Section 1231.3; and, ☒ ☐ ☐ 8. Have accessible a shower in the secure portion of the facility. ☒ ☐ ☐ 1231.2.5 Safety cell. Only the East facility has safety cells, the A safety cell shall: West facility does not. 1. Contain a minimum of 48 square feet (4.5 m2) of floor area with no one floor dimension being less ☒ ☐ ☐ than 6 feet (1829 mm) and a clear ceiling height of 8 feet (2438 mm) or more; 2. Be limited to one inmate; ☒ ☐ ☐ 3. Contain a flushing ring toilet, capable of accepting solid waste, mounted flush with the floor, the controls for which must be located outside of the ☒ ☐ ☐ cell; 4. Be padded as specified in Section 1231.3; ☒ ☐ ☐ 5. Be equipped with a variable intensity, security- type lighting fixture which is inaccessible to the inmate occupant, control of which is located outside ☒ ☐ ☐ of the cell; 6. Provide one or more vertical view panels not more than 4 inches (102 mm) wide nor less than 24 inches (610 mm) long which shall provide a view of ☒ ☐ ☐ the entire room; 7. Provide a food pass with lockable shutter, no more than 4 inches (102 mm) high, and located between 26 inches (660 mm) and 32 inches (813 ☒ ☐ ☐ mm) as measured from the bottom of the food pass to the floor; and, 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 2 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 8. Any wall or ceiling mounted devices must be inaccessible to the inmate occupant. ☒ ☐ ☐ 1231.2.6 Single-occupancy cells. Single-occupancy cells shall: ☒ ☐ ☐ 1. Have a maximum capacity of one inmate; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☒ ☐ ☐ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☒ ☐ ☐ mm); 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☒ ☐ ☐ 5. Contain a bunk, desk and seat as specified in Section 1231.3. ☒ ☐ ☐ Exception: A Type I facility does not require a desk and seat. 1231.2.7 Double-occupancy cells. Double-occupancy cells shall: ☒ ☐ ☐ 1. Have a maximum capacity of two inmates; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☒ ☐ ☐ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☒ ☐ ☐ mm); 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☒ ☐ ☐ 5. Contain two bunks, and at least one desk and seat as specified in Section 1231.3. ☒ ☐ ☐ Exception: A Type I facility does not require a desk and seat. 1231.2.8 Dormitories. There are no dormitories at this facility. Dormitories shall: 1. Contain a minimum of 50 square feet (4.7 m2) of floor area per inmate for a single-bed unit; a minimum of 70 square feet (7 m2) for a double-bed ☐ ☐ ☒ unit; and a minimum of 90 square feet (9.3 m2) for triple-bed unit and have a minimum ceiling height of 8 feet (2438 mm); 2. Be designed for no more than 64 inmates and no fewer than four inmates; ☐ ☐ ☒ 3. Provide access to water closets separate from the wash basin and drinking fountains as specified ☐ ☐ ☒ in Section 1231.3; and 4. In other than Type I facilities, provide storage space for personal items and clothing for each ☐ ☐ ☒ occupant. 1231.2.9 Dayrooms. Dayrooms or dayroom space shall: 1. Contain 35 square feet (3.3 m2) of floor area per ☒ ☐ ☐ inmate in width in front of cells/rooms; 2. Contain tables and seating to accommodate the maximum number of inmates; ☒ ☐ ☐ 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 3 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 3. Provide access to water closets, wash basins and drinking fountains as specified in Section ☒ ☐ ☐ 1231.3; 4. Provide access to a shower or showers as specified in Section 1231.3; and ☒ ☐ ☐ 5. Be provided to all inmates in Type II and Type III facilities (except those housed in special-use cells) and to inmate workers in Type I facilities. Dayroom space as described in this section may be a part of a single occupancy cell used for administrative ☒ ☐ ☐ segregation or a dormitory, in which case the floor area of the cell or a dormitory must be increased by the square footage required for the dayroom. 1231.2.10 Exercise area. An outdoor exercise area or areas must be provided in every Type II and Type III facility. The minimum clear height must be 15 feet (4572 mm) and the minimum number of square feet of surface area will be computed ☒ ☐ ☐ by multiplying 80 percent of maximum rated population by 50 square feet (4.7 m2) and dividing the result by the number of one-hour exercise periods per day. The exercise area must contain or provide free access to a toilet, wash basin, and drinking fountain as ☒ ☐ ☐ provided in Section 1231.3. There must be at least one exercise area of not less than 600 square feet (55.7 m2). The design shall facilitate security and supervision appropriate to the ☒ ☐ ☐ level of custody. Type IV facilities shall have an outdoor recreation area or access to community recreation facilities. ☒ ☐ ☐ 1231.2.11 Correctional program/multipurpose space. An area for correctional programming must be provided in every Type II and Type III facility. The program area ☒ ☐ ☐ and furnishings shall be designed to meet the needs specified by the facility’s program statement. Type IV facilities shall have multipurpose space for games and activities, dining, visiting, TV meetings and quiet space for study and reading, such that activities ☐ ☐ ☒ do not conflict with each other. 1231.2.12 Medical examination room. There must be a minimum of one suitably equipped medical examination room in every facility which provides on-site health care. The examination room shall be designed in consultation with the responsible ☒ ☐ ☐ physician/health authority. Such a medical examination room shall: 1. Be located within the security area and provide for privacy of the inmates; ☒ ☐ ☐ 2. Provide not less than 100 square feet (9.3 m2) of floor space with no single dimension less than 7 feet ☒ ☐ ☐ (2134 mm); 3. Provide hot and cold running water; ☒ ☐ ☐ 4. Provide lockable storage for medical supplies; ☒ ☐ ☐ 5. Provide an examination table; ☒ ☐ ☐ 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 4 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 6. Provide adequate lighting; and ☒ ☐ ☐ 7. Any room where medical procedures are provided must be equipped with hot and cold ☒ ☐ ☐ running water 1231.2.13 Pharmaceutical storage space. Provide lockable storage space for medical supplies and pharmaceutical preparations as ☒ ☐ ☐ referenced by Title 15, California Code of Regulations, Section 1216. 1231.2.14 Medical care housing. There shall be some means to provide medical care ☒ ☐ ☐ and housing of ill and/or infirm inmates. When the program statement for a Type II or Type III facility indicates that medical care housing is needed, such housing must provide lockable storage space for medical instruments and must be located within the ☒ ☐ ☐ security area of the facility accessible to both female and male inmates, but not in the living area of either. The medical care housing unit shall be designed in consultation with the health authority. ☒ ☐ ☐ Medical/mental health areas may contain other than single occupancy cells. ☒ ☐ ☐ If negative pressure isolation rooms are being planned, H101 has a curtain inside, however the room they shall be designed to recognized industry is rarely used and only for non-ambulatory ☒ ☐ ☐ standards. inmates. Curtains are tear-a-way type. 1231.2.16 Commissary. In all Type II, III and IV facilities, except where community access is available, there shall be provisions made for inmates to purchase items (such ☒ ☐ ☐ as candy, toilet articles, stationery supplies, books, newspapers and magazines, etc.). An area shall be provided for the secure storage of the stock for such inmate canteen items. ☒ ☐ ☐ 1231.2.17 Dining facilities. Dining occurs in the dayrooms or cells. In all Type II, III and IV facilities which serve meals, dining areas shall be provided which will allow groups ☒ ☐ ☐ of inmates to dine together. Such dining areas shall not contain toilets, wash basins or showers in the same room without appropriate visual ☒ ☐ ☐ barrier. Wherever the facility contains a central dining room or rooms, it shall contain a minimum of 15 square feet (1.4 m2) of floor space and sufficient tables and seating for ☐ ☐ ☒ each inmate being fed. 1231.2.18 Visiting space. Space shall be provided in all Types I, II, III and IV ☒ ☐ ☐ facilities for visiting. 1231.2.19 Safety equipment storage. A secure area shall be provided for the storage of safety equipment such as fire extinguishers, self-contained ☒ ☐ ☐ breathing apparatus, wire and barcutters, emergency lights, etc.. 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 5 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.20 Janitors’ closet. In Type II facilities, at least one securely lockable janitors’ closet with sufficient area for the storage of ☒ ☐ ☐ cleaning implements and supplies must be provided within the security areas of the facility A mop sink shall also be available within the security area of the facility. In court holding, temporary holding, Types I, III and IV facilities, the closet need not be in the ☒ ☐ ☐ security area. 1231.2.21 Storage rooms. One or more storage rooms shall be provided to accommodate a minimum of 80 cubic feet (2.3 m3) of storage area per inmate for inmate clothing and personal property, institutional clothing, bedding and ☒ ☐ ☐ supplies. Court holding, temporary holding and Type I facilities may be excluded from the storage space requirement for personal and institutional clothing unless clothing is issued. 1231.2.22 Audio monitoring system. In court holding, temporary holding, Type I, Type II and Type II facilities there shall be an inmate- or sound- actuated audio monitoring system in temporary holding cells or rooms, temporary staging cells or rooms, sobering cells, safety cells, single and double ☒ ☐ ☐ occupancy cells, dormitories, dayrooms, exercise areas and correctional program/multipurpose space, which is capable of alerting personnel who can respond immediately. 1231.2.23 Laundry facilities. In Type IV facilities, provision shall be made for washing and drying personal clothing by machines, ☒ ☐ ☐ either in the facility or in the community, if access is permitted for same. 1231.2.24 Emergency power. There shall be a source of emergency power in all detention facilities capable of providing minimal lighting in all housing units, activities areas, corridors, stairs and ☒ ☐ ☐ central control points, and to maintain fire and life safety, security, communications and alarm systems. Such an emergency power source shall conform to the requirements specified in Title 24, Part 3, Article 700, California Electrical Code, California Code of ☒ ☐ ☐ Regulations. 1231.2.25 Confidential interview rooms. There must be a minimum of one suitably furnished interview room for confidential interviews in every facility which provides onsite health care. The interview room shall be designed in consultation with responsible ☒ ☐ ☐ custodial staff and health care staff. Such an interview room shall: 1. Be located within the security area accessible to both female and male inmates; and ☒ ☐ ☐ 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 6 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 2. Provide not less than 70 square feet (6.5 m2) of floor space with no single dimension less than 6 feet ☒ ☐ ☐ (1829 mm). 1231.2.26 Attorney interview space. All facilities except Type IV facilities shall include attorney interview areas which provide for ☒ ☐ ☐ confidential consultation with inmates. 1231.3.1 Toilets/urinals. 1. Toilets/urinals must be provided in single- ☒ ☐ ☐ occupancy cells and double-occupancy cells. 2. In dormitories, toilets/urinals must be provided in a ratio to inmates of 1:10. ☐ ☐ ☒ 3. Toilets/urinals must be accessible to the occupants of day-rooms and exercise areas. ☒ ☐ ☐ 4. In temporary holding cells and temporary staging cells toilets/urinals must be provided in a ratio to ☒ ☐ ☐ inmates of 1:16. 5. In sobering cells toilets/urinals must be provided in a ratio to inmates of 1:8. ☒ ☐ ☐ 6. One urinal or 2 feet (610 mm) of urinal trough may be substituted for each toilet up to one third of the total number of toilets required, except in those ☒ ☐ ☐ facilities or portions thereof used for females. 7. Toilet areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.2 Wash basins. 1. Wash basins must be provided in single ☒ ☐ ☐ occupancy cells and double occupancy cells. 2. In dormitories, wash basins must be provided in a ratio to inmates of 1:10. ☐ ☐ ☒ 3. Wash basins must be accessible to the occupants of day-rooms and exercise areas ☒ ☐ ☐ 4. In temporary holding cells and temporary staging cells, wash basins must be provided in a ratio to ☒ ☐ ☐ inmates of 1:16. 5. In sobering cells, wash basins must be provided in a ratio to inmates of 1:8. ☒ ☐ ☐ 6. Wash basins must be provided with hot and cold or tempered water. ☒ ☐ ☐ 7. Two feet (610 mm) of wash basin trough may be substituted for each basin required. ☐ ☐ ☒ 1231.3.3 Drinking fountains. There must be a minimum of one drinking fountain in every single-occupancy cell, double-occupancy cell, dormitory, temporary holding cell, temporary staging ☒ ☐ ☐ cell, sobering cell, and be accessible to the occupants of day rooms and exercise areas. Additional drinking fountains shall be located in other areas of the facility so that drinking water will be ☒ ☐ ☐ available to inmates and staff. 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 7 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS Such drinking fountains must meet the following minimum health requirements: 1. The drinking fountain bubbler shall be on an ☒ ☐ ☐ angle which prevents waste water from flowing over the drinking fountain bubbler. 2. Water flow shall be actuated by mechanical means. ☒ ☐ ☐ 1231.3.4 Showers Must be available to all inmates on a ratio of at least one shower to every 20 inmates or fraction thereof and ☒ ☐ ☐ must provide hot and cold water or tempered water. Shower stalls/shower areas must be designed and constructed of materials which are impervious to water ☒ ☐ ☐ and soap so they may be easily cleaned. Shower areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.5 Beds Must be elevated off the floor, have a solid bottom, and a sleeping surface of at least 30 inches (762 mm) wide ☒ ☐ ☐ and 76 inches (1930 mm) long. Multiple beds must have a minimum of 21 inches (533 mm) between bed pans. ☒ ☐ ☐ Except in minimum security areas, beds must be securely fastened to the floor or the wall. ☒ ☐ ☐ 1231.3.6 Lighting. Lighting in housing units, dayrooms and activity areas must be sufficient to permit easy reading by a person with normal vision, and shall not be less than 20 ☒ ☐ ☐ footcandles (215.2 lux) at desk level and in the grooming area. Lighting shall be centrally controlled and/or occupant controlled in housing cells or rooms. ☒ ☐ ☐ Night lighting in these areas shall be sufficient to give good visibility for purposes of supervision ☒ ☐ ☐ In minimum-security areas, lighting may be supplied by ordinary lighting fixtures, and in areas of higher ☒ ☐ ☐ security, light fixtures must be of secure design. 1231.3.7 Windows. In housing areas of higher than minimum security, exterior windows which are constantly accessible to inmates for escape must be designed and constructed ☒ ☐ ☐ so that if broken out, the net area accessible for escape is no greater than 5 inches (127 mm) in one dimension. 1231.3.8 Cell padding. In sobering cells, the floor and partition shall be padded. ☒ ☐ ☐ In safety cells, padding must cover the entire floor, doors, and walls and everything on them to a clear ☒ ☐ ☐ height of 8 feet (2438 mm). All such padded cells must be equipped with a tamper resistant fire sprinkler as approved by the State Fire Marshal. ☒ ☐ ☐ All padding must be: 1. Approved for use by the State Fire Marshal; ☒ ☐ ☐ 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 8 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 2. Nonporous to facilitate cleaning; ☒ ☐ ☐ 3. At least 1/2-inch (12.7 mm) thick; ☒ ☐ ☐ 4. Of a unitary or laminated construction to prevent its destruction by teeth, hand tearing or small metal ☒ ☐ ☐ objects; 5. Firmly bonded to all padded surfaces to prevent tearing or ripping; and ☒ ☐ ☐ 6. Without any exposed seams susceptible to tearing or ripping. ☒ ☐ ☐ 1231.3.9 Mirrors. A mirror of a material appropriate to the level of security must be provided near each wash basin specified in ☒ ☐ ☐ these regulations. 1231.3.10 Seating. In temporary holding and temporary staging cells, ☒ ☐ ☐ seating must be securely fixed to the floor and/or wall. When bench seating is used, 18 inches (457 mm) of bench is seating for one person. ☒ ☐ ☐ 1231.3.11 Table/seat. In single- and double-occupancy cells, a table and seat for the purpose of writing and dining shall be provided. ☒ ☐ ☐ Exception: A Type I facility does not require a table and a seat. 1231.3.12 Weapons locker. (20-22) Located outside of the secure area. A secure weapons locker shall be located outside the ☒ ☐ ☐ security perimeter of the facility Such weapons lockers shall be equipped with individual compartments, each with an individual locking device. ☒ ☐ ☐ Weapons lockers are required in temporary and court holding facilities and in all facilities of higher than ☒ ☐ ☐ minimum security. Design Requirements (102(c)6) Design requirements as specified in Title 24, Part 1, 102(c)6 are met. (See regulation for specific requirements. Note areas of non-compliance that are ☒ ☐ ☐ applicable to the facility type and construction date in the "comments" section.) 5730 Stanislaus Public Safety Center East/West Facility II PHY 23-24 - 9 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TYPE II AND III FACILITIES Board of State and Community Corrections PROCEDURES1 BSCC Code: 5735 FACILITY NAME: Stanislaus REACT Center FACILITY TYPE: II PERSON(S) INTERVIEWED: Sgt. Flores, Sgt. Johnson, Sgt. Ballard, Dep. Delgadillo FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS 1027.5 SAFETY CHECKS SCSDPPMADD 9-01.01 Security Inspections SCSDPPMADD 9-01.06 Electronic The facility administrator shall develop and implement Documentation System policy and procedures for conducting safety checks that include, but are not limited to, the following: ☒ ☐ ☐ (a) Safety checks will determine the safety and well- being of individuals and shall be conducted at least hourly through direct visual observation of all people held and housed in the facility. (b) There shall be no more than a 60-minute lapse Approximately three consecutive months of between safety checks. safety check logs were requested for this inspection. For the logs inspected, ☒ ☐ ☐ compliance was verified. When the few late safety checks did occur, they were highlighted and a memo indicating why the employee performed the check late. (c) Safety checks for people in sobering cells, safety cells, and restraints shall occur more frequently as ☒ ☐ ☐ outlined in section 1055, section 1056, and section 1058 of these regulations. (d) Safety checks shall occur at random or varied ☒ ☐ ☐ intervals. (e) There shall be a written plan that includes the documentation of all safety checks. Documentation shall include: ☒ ☐ ☐ (1) the actual time at which each individual safety check occurred; (2) the location where each individual safety check occurred, such as a cell, module, or dormitory ☒ ☐ ☐ number; and, (3) Initials or employee identification number of staff ☒ ☐ ☐ who completed the safety check(s). 1 This document is intended for use as a tool during the targeted inspection process; this worksheet may not contain each Title 15 regulation that is required. Additionally, many regulations on this worksheet are SUMMARIES of the regulation; the text on this worksheet may not contain the entire text of the actual regulation. Please refer to the complete California Code of Regulations, Title 15, Minimum Standards for Local Facilities, Division 1, Chapter 1, Subchapter 4 for the complete list and text of regulations. 5735 Stanislaus REACT Center II PRO 23-24 Page 1 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (f) A documented process by which safety checks are reviewed at regular defined intervals by a supervisor or facility manager, including methods of mitigating ☒ ☐ ☐ patterns of inconsistent documentation, or untimely completion of, safety checks. 1032 FIRE SUPPRESSION PREPLANNING SCSDPPMADD 10-01.01 Fire Suppression Planning Pursuant to Penal Code Section 6031.1(b), the facility administrator shall consult with the local fire department ☒ ☐ ☐ having jurisdiction over the facility, with the State Fire Marshal, or both, in developing a plan for fire suppression which shall include, but not be limited to: (a) a fire suppression pre-plan developed with the local fire department to be included as part of the policy and ☒ ☐ ☐ procedures manual (Title 15, California Code of Regulations Section 1029); (b) monthly fire prevention inspections by facility staff ☒ ☐ ☐ with two-year retention of the inspection record; (c) fire prevention inspections as required by Health and Safety Code Section 13146.1(a) and (b) which requires ☒ ☐ ☐ inspections at least once every two years; (d) an evacuation plan; and, ☒ ☐ ☐ (e) a plan for the emergency housing of incarcerated ☒ ☐ ☐ people in the case of fire. 1056 USE OF SOBERING CELL This facility does not have a sobering cell. The sobering cell described in Title 24, Part 2, Section ☐ ☐ ☒ 1231.2.4, shall be used for temporary holding of incarcerated people who are a threat to their own safety or the safety of others due to their state of intoxication. A person shall be removed from the sobering cell as soon as they are able to continue the admission process ☐ ☐ ☒ or are no longer a risk to themselves or others. In no case shall a person remain in a sobering cell over six hours without an evaluation by medical or custody staff to determine whether the person has an urgent ☐ ☐ ☒ medical problem, pursuant to section 1213 of these regulations. At 12 hours from the time of placement, all persons must ☐ ☐ ☒ receive an evaluation by responsible health care staff. Intermittent direct visual observation of people held in the sobering cell shall be conducted no less than every ☐ ☐ ☒ half hour. Such observation shall be documented. 5735 Stanislaus REACT Center II PRO 23-24 Page 2 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS 1058 USE OF RESTRAINT DEVICES This facility does not use restraints. The facility administrator, in cooperation with the responsible physician, shall develop and implement written policies and procedures for the use of restraint devices. Restraint devices include any devices which immobilize extremities or prevent the incarcerated ☐ ☐ ☒ person from being ambulatory. The provisions of this section do not apply to the use of handcuffs, shackles, or other restraint devices when used to restrain incarcerated people for security reasons. The facility manager may delegate authority to place an incarcerated person in restraints to responsible health care staff. (a) The policy shall address the following areas: ☐ ☐ ☒ (1) acceptable restraint devices; (2) signs or symptoms which should result in immediate medical/mental health referral; ☐ ☐ ☒ availability of cardiopulmonary resuscitation equipment; (3) protective housing of restrained persons; ☐ ☐ ☒ (4) provision for hydration and sanitation needs; and, ☐ ☐ ☒ (5) exercising of extremities. ☐ ☐ ☒ (b) Policy shall also include, but not be limited to, the following requirements: ☐ ☐ ☒ (1) In no case shall restraints be used for punishment or as a substitute for treatment. (2) Restraint devices shall only be used on incarcerated people who display behavior which ☐ ☐ ☒ results in the destruction of property or reveal an intent to cause physical harm to self or others. (3) Restraint devices should be used only when less restrictive alternatives, including verbal de- ☐ ☐ ☒ escalation techniques, have been attempted and are deemed ineffective. (4) An incarcerated person shall be placed in restraints only with the approval of the facility manager, the facility watch commander, or ☐ ☐ ☒ responsible health care staff; continued retention shall be reviewed a minimum of every hour. (5) Continuous direct visual observation shall be ☐ ☐ ☒ maintained until a medical opinion can be obtained. (6) A medical opinion on placement and retention shall be secured within one hour from the time of ☐ ☐ ☒ placement. (7) A medical assessment shall be completed within ☐ ☐ ☒ four hours of placement. 5735 Stanislaus REACT Center II PRO 23-24 Page 3 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (8) Continuous direct visual observation shall be conducted at least twice every 30 minutes to ensure that the restraints are properly employed, and to ensure the safety and well-being of the incarcerated person. Such observation shall be documented. ☐ ☐ ☒ While in restraint devices all incarcerated persons shall be housed alone or in a specified housing area which makes provisions to protect the person from abuse. (9) If the facility manager, or designee, in consultation with responsible health care staff determines that an incarcerated person cannot be ☐ ☐ ☒ safely removed from restraints after eight hours, the person shall be taken to a medical facility for further evaluation. (10) Where applicable, the facility manager shall use the restraint device manufacturer’s recommended ☐ ☐ ☒ maximum time limits for placement. (11) All events and information related to the placement in restraints shall be documented and shall be video recorded unless exigent circumstances prevent staff from doing so. The ☐ ☐ ☒ documentation shall include: the reason for placement; person authorizing placement; names of staff involved in the placement; injuries sustained; and the duration of placement. 1065 EXERCISE AND OUT OF CELL TIME SCSDPPMADD 04-01.25 Yard Deputy (a) The facility administrator of a Type II or III facility shall This facility is of modular design. ☒ ☐ ☐ develop written policies and procedures for a minimum Incarcerated persons have daily access to the of 10 hours of out of cell time distributed over a period of dayroom. seven days to include: (1) an opportunity for three hours of exercise and One large exercise yard is used by each of the modules in this facility. A review of the documentation provided verified that each ☒ ☐ ☐ module has the opportunity for exercise several times per week and for a minimum of three hours. (2) an opportunity for seven hours of recreation. ☒ ☐ ☐ Policies shall include reasonable and necessary ☒ ☐ ☐ procedures to ensure safety and security. 5735 Stanislaus REACT Center II PRO 23-24 Page 4 of 4 A353 Type II & III Targeted PRO eff 01.2024 ADULT DETENTION FACILITY LIVING AREA SPACE EVALUATION Board of State and Community Corrections BSCC Code: 5735 FACILITY: Stanislaus County REACT Center TYPE: II RC: 288 FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S Note: Originally numbered #5730 as part of the Public Safety Center, in May 2018, this independent facility (constructed in part with SB 1022 financing) was given the number #5735. Intake P101 Holding 2010 1 - - (1) 9"4" x 7'10" 1 1 1 Note: Bench seating 4'; chase 2 sq. ft. ADA cell. P102 Holding 2010 1 - - (1) 9"4" x 6'8" 1 1 1 Note: Bench seating 3'; chase 2 sq. ft. Housing N100 – Level 1 N101 Dorm 2010 1 8 8 8 20' x 14' N102 Dorm 2010 1 8 8 8 20' x 14' Note: Dayroom 1,986 square feet /35 = 56. (23-34) N100 is the entire unit, N101, N102, N103, N104, N105, and N106 are dormitories within N100. A common restroom is located on each floor (level) each containing 3 toilets, 3 washbasins, 3 fountains, and 2 showers Level 2 N103 Dorm 2010 1 8 8 8 20' x 14' N104 Dorm 2010 1 8 8 8 20' x 14' N105 Dorm 2010 1 8 8 8 20' x 14' N106 Dorm 2010 1 8 8 8 20' x 14' Note: Each dorm in this unit contains 280 square feet/70 (double-bed unit) = 4 x 2 (double-bed unit) = 8. Dry rooms. Level 1&2: 2 Toilets; 3 washbasins (each with bubbler/fountain); 2 showers. Six tables with eight seats (removable for ADA). Housing N200 N201 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N202 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N203 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N204 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N205 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N206 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 Note: Dayroom is 1,986 square feet/35 = 56. (20-22) N202 is an ADA cell. (23-34) N200 is the entire unit, N201, N202, N203, N204, N205, and N206 are dormitories within N200. A common restroom is located on each floor (level) each *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5735 Stanislaus REACT Center II LASE 23-24 - 1 - A360 LAS Adult-05.dot (8/05) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S containing 3 toilets, 3 washbasins, 3 fountains, and 2 showers. Each dorm in this unit contains 296 square feet/70 (double- bed unit) = 4 x 2 (double-bed unit) = 8. Six tables with eight seats (removable for ADA). Housing N300 N301 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N302 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N303 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N304 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N305 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 N306 Dorm 2010 1 8 8 8 19'4" x 15'4" 1 1 1 Note: Each dorm in this unit contains 296 square feet/70 (double-bed unit) = 4 x 2 (double-bed unit) = 8. Six tables with eight seats (removable for ADA). The dayroom is 1,986 square feet/35 = 56. (20-22) N302 is an ADA cell. A common restroom is located on each floor (level) each containing 3 toilets, 3 washbasins, 3 fountains, and 2 showers. Housing N400 N401 Dorm 2010 1 8 8 8 20' x 14' N402 Dorm 2010 1 8 8 8 20' x 14' N403 Dorm 2010 1 8 8 8 20' x 14' N404 Dorm 2010 1 8 8 8 20' x 14' N405 Dorm 2010 1 8 8 8 20' x 14' N406 Dorm 2010 1 8 8 8 20' x 14' Note: Each dorm in this unit contains 280 square feet/70 (double-bed unit) = 4 x 2 (double-bed unit) = 8. Six tables with 8 seats (three seats removed for ADA). The dayroom is 1986 square feet/35 = 56. A common restroom is located on each floor (level) each containing 3 toilets, 3 washbasins, 3 fountains, and 2 showers. Housing O100 O101 Dorm 2010 1 8 8 8 21'4" x 15'4" 1 1 1 O102 Dorm 2010 1 8 8 8 15'4" x 21'5" 1 1 1 O103 Dorm 2010 1 8 8 8 15'4" x 21'5" 1 1 1 O104 Dorm 2010 1 8 8 8 15'4" x 21'5" 1 1 1 Note: Each dorm on this level contains 328 square feet/70 (double-bed unit) = 4 x 2 (double-bed unit) = 8. Six tables with eight seats (removable for ADA). The dayroom is 1639 square feet/35=46. The dayroom contains 3 showers. (2024) This housing unit is not currently being used. Housing O300 O301 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 O302 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 O303 Dorm 2010 1 4 4 4 13'4" x 12'8" 1 1 1 O304 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 O305 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5735 Stanislaus REACT Center II LASE 23-24 - 2 - A360 LAS Adult-05.dot (8/05) ROOMS EACH ROOM Cell Applicable # EACH CELL Total DIMENSIONS FIXTURES* Location Type Standards Cells # Beds RC RC (L x W x H) T U W F S O306 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 O307 Dorm 2010 1 4 4 4 13'4" x 12' 1 1 1 O308 Dorm 2010 1 4 4 4 13'4" x 12'8" 1 1 1 Note: Each dorm in this unit contains between 160 and 169 square feet/70 (double-bed unit) = 2 x 2 (double-bed unit) = 4. Six tables with eight seats (removable for ADA). The dayroom is 1619 square feet/32 = 50. Two showers are located in the dayroom. Housing O400 O401 Dorm 2010 1 8 8 8 21'4" x 15'4" 1 1 1 O402 Dorm 2010 1 8 8 8 15'4" x 20'8" 1 1 1 O403 Dorm 2010 1 8 8 8 15'4" x 20'8" 1 1 1 O404 Dorm 2010 1 8 8 8 15'4" x 20'8" 1 1 1 Note: Each dorm in this unit contains between 317 and 327 square feet/70 (double-bed unit) = 4 x 2 (double-bed unit) = 8. Six tables with eight seats (removable for ADA). The dayroom is 1618 square feet/35 = 45. Three showers are in the dayroom. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5735 Stanislaus REACT Center II LASE 23-24 - 3 - A360 LAS Adult-05.dot (8/05) ADULT TYPE I, II, III AND IV FACILITIES PHYSICAL PLANT EVALUATION The Board of State and Community Corrections APPLICABLE TITLE 24 REGULATIONS: 6/94; 2/99; 2001; 2005; 2008; 2010, 2013, 2017 BSCC Code: 5735 FACILITY NAME: Stanislaus REACT Center FACILITY TYPE: II 6/94: 2/99: 2001: 2005: 2008: 2010: ☐ ☐ ☐ ☐ ☐ ☒ APPLICABLE REGULATIONS (Check All That Apply): 2013: ☐ 2017: ☐ ☐ ☐ ☐ ☐ FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.1 Reception and booking. Booking occurs in an adjacent facility. Facilities where booking and housing occur shall have the following space and equipment: ☒ ☐ ☐ 1. Weapons locker as specified in Section 1231.3.12. 2. A cell or room for the confinement of inmates pending their booking, complying with Section ☒ ☐ ☐ 1231.2.2. 3. A sobering cell as described in Section 1231.2.4 if intoxicated, inmates who may pose a danger to ☐ ☐ ☒ themselves or others are held. For those facilities that accept male and female intoxicated inmates two sobering cells shall be ☐ ☐ ☒ provided. 4. Access to a shower within the secure portion of the facility. ☐ ☐ ☒ 5. Provide access to a secure vault or storage When an inmate is transferred to this facility space for inmate valuables. their personal property follows them and is secured in a storage area. At the time of ☒ ☐ ☐ release, the inmate is returned all the property they had at booking. 1231.2.2 Temporary holding cell or room. A temporary holding cell or room shall: 1. Contain a minimum of 10 square feet (0.93 m2) ☒ ☐ ☐ of floor area per inmate; 2. Be limited to no more than 16 inmates; ☒ ☐ ☐ 3. Be no smaller than 40 square feet (3.7 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☒ ☐ ☐ more; 4. Contain seating to accommodate all inmates as required in Section 1231.3; ☒ ☐ ☐ 5. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☒ ☐ ☐ 6. Maximize visual supervision of inmates by staff; and ☒ ☐ ☐ 7. When located in a temporary holding facility, the cell or room shall be equipped with a bunk if inmates ☒ ☐ ☐ are to be held longer than 12 hours. 5735 Stanislaus REACT Center II PHY 23-24 - 1 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.3 Temporary staging cell or room. No temporary staging cells at this facility. A temporary staging cell or room shall: 1. Be constructed for the purpose of holding inmates who have been classified and segregated ☐ ☐ ☒ in accordance with Sections 1050 and 1053 of Title 15, Division 1, California Code of Regulations. 2. Be limited to holding inmates up to four hours. ☐ ☐ ☒ 3. Be limited to no more than 80 inmates. ☐ ☐ ☒ 4. Contain a minimum of 10 square feet (0.93 m2) of floor area per inmate and a clear ceiling height of ☐ ☐ ☒ 8 feet (2438 mm) or more. 5. Be no smaller than 160 square feet (14.9 m2). ☐ ☐ ☒ 6. Contain seating to accommodate all inmates as required in Section 1231.3. ☐ ☐ ☒ 7. Contain toilet, wash basin and drinking fountain as specified in Section 1231.3. ☐ ☐ ☒ 8. Maximize visual supervision of inmates by staff. ☐ ☐ ☒ 1231.2.4 Sobering cell. No sobering cell at this facility. A sobering cell shall: 1. Contain a minimum of 20 square feet (1.9 m2) of ☐ ☐ ☒ floor area per inmate; 2. Be limited to eight inmates; ☐ ☐ ☒ 3. Be no smaller than 60 square feet (5.6 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☐ ☐ ☒ more; 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☐ ☐ ☒ 5. Have padded partitions located next to toilet fixture in such a manner that they provide support ☐ ☐ ☒ to the user; 6. Maximize visual supervision of inmates by staff; ☐ ☐ ☒ 7. Be padded on the floor as specified in Section 1231.3; and, ☐ ☐ ☒ 8. Have accessible a shower in the secure portion of the facility. ☐ ☐ ☒ 1231.2.5 Safety cell. No safety cell at this facility. A safety cell shall: 1. Contain a minimum of 48 square feet (4.5 m2) of floor area with no one floor dimension being less ☐ ☐ ☒ than 6 feet (1829 mm) and a clear ceiling height of 8 feet (2438 mm) or more; 2. Be limited to one inmate; ☐ ☐ ☒ 3. Contain a flushing ring toilet, capable of accepting solid waste, mounted flush with the floor, the controls for which must be located outside of the ☐ ☐ ☒ cell; 4. Be padded as specified in Section 1231.3; ☐ ☐ ☒ 5. Be equipped with a variable intensity, security- type lighting fixture which is inaccessible to the inmate occupant, control of which is located outside ☐ ☐ ☒ of the cell; 5735 Stanislaus REACT Center II PHY 23-24 - 2 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 6. Provide one or more vertical view panels not more than 4 inches (102 mm) wide nor less than 24 inches (610 mm) long which shall provide a view of ☐ ☐ ☒ the entire room; 7. Provide a food pass with lockable shutter, no more than 4 inches (102 mm) high, and located between 26 inches (660 mm) and 32 inches (813 ☐ ☐ ☒ mm) as measured from the bottom of the food pass to the floor; and, 8. Any wall or ceiling mounted devices must be inaccessible to the inmate occupant. ☐ ☐ ☒ 1231.2.6 Single-occupancy cells. No single-occupancy cells at this facility. Single-occupancy cells shall: ☐ ☐ ☒ 1. Have a maximum capacity of one inmate; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☐ ☐ ☒ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☐ ☐ ☒ mm); 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☐ ☐ ☒ 5. Contain a bunk, desk and seat as specified in Section 1231.3. ☐ ☐ ☒ Exception: A Type I facility does not require a desk and seat. 1231.2.7 Double-occupancy cells. No double-occupancy cells at this facility. Double-occupancy cells shall: ☐ ☐ ☒ 1. Have a maximum capacity of two inmates; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☐ ☐ ☒ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☐ ☐ ☒ mm); 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☐ ☐ ☒ 5. Contain two bunks, and at least one desk and seat as specified in Section 1231.3. ☐ ☐ ☒ Exception: A Type I facility does not require a desk and seat. 1231.2.8 Dormitories. All double bunks Dormitories shall: 1. Contain a minimum of 50 square feet (4.7 m2) of 4 – 48 bed dorms = 192. floor area per inmate for a single-bed unit; a 3 – 32 bed dorms = 96. minimum of 70 square feet (7 m2) for a double-bed ☒ ☐ ☐ unit; and a minimum of 90 square feet (9.3 m2) for triple-bed unit and have a minimum ceiling height of 8 feet (2438 mm); 2. Be designed for no more than 64 inmates and no fewer than four inmates; ☒ ☐ ☐ 3. Provide access to water closets separate from the wash basin and drinking fountains as specified ☒ ☐ ☐ in Section 1231.3; and 5735 Stanislaus REACT Center II PHY 23-24 - 3 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 4. In other than Type I facilities, provide storage space for personal items and clothing for each ☒ ☐ ☐ occupant. 1231.2.9 Dayrooms. Dayrooms or dayroom space shall: 1. Contain 35 square feet (3.3 m2) of floor area per ☒ ☐ ☐ inmate in width in front of cells/rooms; 2. Contain tables and seating to accommodate the maximum number of inmates; ☒ ☐ ☐ 3. Provide access to water closets, wash basins and drinking fountains as specified in Section ☒ ☐ ☐ 1231.3; 4. Provide access to a shower or showers as specified in Section 1231.3; and ☒ ☐ ☐ 5. Be provided to all inmates in Type II and Type III facilities (except those housed in special-use cells) and to inmate workers in Type I facilities. Dayroom space as described in this section may be a part of a single occupancy cell used for administrative ☒ ☐ ☐ segregation or a dormitory, in which case the floor area of the cell or a dormitory must be increased by the square footage required for the dayroom. 1231.2.10 Exercise area. An outdoor exercise area or areas must be provided in every Type II and Type III facility. The minimum clear height must be 15 feet (4572 mm) and the minimum number of square feet of surface area will be computed ☒ ☐ ☐ by multiplying 80 percent of maximum rated population by 50 square feet (4.7 m2) and dividing the result by the number of one-hour exercise periods per day. The exercise area must contain or provide free access to a toilet, wash basin, and drinking fountain as ☒ ☐ ☐ provided in Section 1231.3. There must be at least one exercise area of not less than 600 square feet (55.7 m2). The design shall facilitate security and supervision appropriate to the ☒ ☐ ☐ level of custody. Type IV facilities shall have an outdoor recreation area or access to community recreation facilities. ☒ ☐ ☐ 1231.2.11 Correctional program/multipurpose space. An area for correctional programming must be provided in every Type II and Type III facility. The program area ☒ ☐ ☐ and furnishings shall be designed to meet the needs specified by the facility’s program statement. Type IV facilities shall have multipurpose space for games and activities, dining, visiting, TV meetings and quiet space for study and reading, such that activities ☐ ☐ ☒ do not conflict with each other. 1231.2.12 Medical examination room. There must be a minimum of one suitably equipped medical examination room in every facility which provides on-site health care. The examination room shall be designed in consultation with the responsible ☒ ☐ ☐ physician/health authority. Such a medical examination room shall: 5735 Stanislaus REACT Center II PHY 23-24 - 4 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1. Be located within the security area and provide for privacy of the inmates; ☒ ☐ ☐ 2. Provide not less than 100 square feet (9.3 m2) of 8’8” x 16’. floor space with no single dimension less than 7 feet 8’ x 15’4”. ☒ ☐ ☐ (2134 mm); 3. Provide hot and cold running water; ☒ ☐ ☐ 4. Provide lockable storage for medical supplies; ☒ ☐ ☐ 5. Provide an examination table; ☒ ☐ ☐ 6. Provide adequate lighting; and ☒ ☐ ☐ 7. Any room where medical procedures are provided must be equipped with hot and cold ☒ ☐ ☐ running water 1231.2.13 Pharmaceutical storage space. Provide lockable storage space for medical supplies and pharmaceutical preparations as ☒ ☐ ☐ referenced by Title 15, California Code of Regulations, Section 1216. 1231.2.14 Medical care housing. No medical care housing at this facility. There shall be some means to provide medical care Inmates needing medical care are transferred ☐ ☐ ☒ and housing of ill and/or infirm inmates. to an adjacent facility. When the program statement for a Type II or Type III facility indicates that medical care housing is needed, such housing must provide lockable storage space for medical instruments and must be located within the ☐ ☐ ☒ security area of the facility accessible to both female and male inmates, but not in the living area of either. The medical care housing unit shall be designed in consultation with the health authority. ☐ ☐ ☒ Medical/mental health areas may contain other than single occupancy cells. ☐ ☐ ☒ If negative pressure isolation rooms are being planned, they shall be designed to recognized industry ☐ ☐ ☒ standards. 1231.2.16 Commissary. In all Type II, III and IV facilities, except where community access is available, there shall be provisions made for inmates to purchase items (such ☒ ☐ ☐ as candy, toilet articles, stationery supplies, books, newspapers and magazines, etc.). An area shall be provided for the secure storage of the stock for such inmate canteen items. ☒ ☐ ☐ 1231.2.17 Dining facilities. Dining occurs in the dayrooms. In all Type II, III and IV facilities which serve meals, dining areas shall be provided which will allow groups ☒ ☐ ☐ of inmates to dine together. Such dining areas shall not contain toilets, wash basins or showers in the same room without appropriate visual ☒ ☐ ☐ barrier. Wherever the facility contains a central dining room or rooms, it shall contain a minimum of 15 square feet (1.4 m2) of floor space and sufficient tables and seating for ☐ ☐ ☒ each inmate being fed. 1231.2.18 Visiting space. Each housing area is equipped with a video Space shall be provided in all Types I, II, III and IV visitation area. Inmates will receive the two ☒ ☐ ☐ facilities for visiting. 30-minute visits. 5735 Stanislaus REACT Center II PHY 23-24 - 5 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.19 Safety equipment storage. A secure area shall be provided for the storage of safety equipment such as fire extinguishers, self-contained ☒ ☐ ☐ breathing apparatus, wire and barcutters, emergency lights, etc.. 1231.2.20 Janitors’ closet. In Type II facilities, at least one securely lockable janitors’ closet with sufficient area for the storage of ☒ ☐ ☐ cleaning implements and supplies must be provided within the security areas of the facility A mop sink shall also be available within the security area of the facility. In court holding, temporary holding, Types I, III and IV facilities, the closet need not be in the ☒ ☐ ☐ security area. 1231.2.21 Storage rooms. One or more storage rooms shall be provided to accommodate a minimum of 80 cubic feet (2.3 m3) of storage area per inmate for inmate clothing and personal property, institutional clothing, bedding and ☒ ☐ ☐ supplies. Court holding, temporary holding and Type I facilities may be excluded from the storage space requirement for personal and institutional clothing unless clothing is issued. 1231.2.22 Audio monitoring system. In court holding, temporary holding, Type I, Type II and Type II facilities there shall be an inmate- or sound- actuated audio monitoring system in temporary holding cells or rooms, temporary staging cells or rooms, sobering cells, safety cells, single and double ☒ ☐ ☐ occupancy cells, dormitories, dayrooms, exercise areas and correctional program/multipurpose space, which is capable of alerting personnel who can respond immediately. 1231.2.23 Laundry facilities. In Type IV facilities, provision shall be made for washing and drying personal clothing by machines, ☐ ☐ ☒ either in the facility or in the community, if access is permitted for same. 1231.2.24 Emergency power. There shall be a source of emergency power in all detention facilities capable of providing minimal lighting in all housing units, activities areas, corridors, stairs and ☒ ☐ ☐ central control points, and to maintain fire and life safety, security, communications and alarm systems. Such an emergency power source shall conform to the requirements specified in Title 24, Part 3, Article 700, California Electrical Code, California Code of ☒ ☐ ☐ Regulations. 1231.2.25 Confidential interview rooms. There must be a minimum of one suitably furnished interview room for confidential interviews in every facility which provides onsite health care. The interview room shall be designed in consultation with responsible ☒ ☐ ☐ custodial staff and health care staff. Such an interview room shall: 5735 Stanislaus REACT Center II PHY 23-24 - 6 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1. Be located within the security area accessible to both female and male inmates; and ☒ ☐ ☐ 2. Provide not less than 70 square feet (6.5 m2) of 8’7” x 9’4”. floor space with no single dimension less than 6 feet 10’7” x 8’6”. ☒ ☐ ☐ (1829 mm). 1231.2.26 Attorney interview space. All facilities except Type IV facilities shall include attorney interview areas which provide for ☒ ☐ ☐ confidential consultation with inmates. 1231.3.1 Toilets/urinals. No single-occupancy cells at this facility. 1. Toilets/urinals must be provided in single- ☐ ☐ ☒ occupancy cells and double-occupancy cells. 2. In dormitories, toilets/urinals must be provided in a ratio to inmates of 1:10. ☒ ☐ ☐ 3. Toilets/urinals must be accessible to the occupants of day-rooms and exercise areas. ☒ ☐ ☐ 4. In temporary holding cells and temporary staging cells toilets/urinals must be provided in a ratio to ☒ ☐ ☐ inmates of 1:16. 5. In sobering cells toilets/urinals must be provided No sobering cells at this facility. in a ratio to inmates of 1:8. ☐ ☐ ☒ 6. One urinal or 2 feet (610 mm) of urinal trough may be substituted for each toilet up to one third of the total number of toilets required, except in those ☐ ☐ ☒ facilities or portions thereof used for females. 7. Toilet areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.2 Wash basins. No single occupancy cells at this facility. 1. Wash basins must be provided in single ☐ ☐ ☒ occupancy cells and double occupancy cells. 2. In dormitories, wash basins must be provided in a ratio to inmates of 1:10. ☒ ☐ ☐ 3. Wash basins must be accessible to the occupants of day-rooms and exercise areas ☒ ☐ ☐ 4. In temporary holding cells and temporary staging cells, wash basins must be provided in a ratio to ☒ ☐ ☐ inmates of 1:16. 5. In sobering cells, wash basins must be provided in a ratio to inmates of 1:8. ☐ ☐ ☒ 6. Wash basins must be provided with hot and cold or tempered water. ☒ ☐ ☐ 7. Two feet (610 mm) of wash basin trough may be substituted for each basin required. ☐ ☐ ☒ 1231.3.3 Drinking fountains. There must be a minimum of one drinking fountain in every single-occupancy cell, double-occupancy cell, dormitory, temporary holding cell, temporary staging ☒ ☐ ☐ cell, sobering cell, and be accessible to the occupants of day rooms and exercise areas. Additional drinking fountains shall be located in other areas of the facility so that drinking water will be ☒ ☐ ☐ available to inmates and staff. 5735 Stanislaus REACT Center II PHY 23-24 - 7 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS Such drinking fountains must meet the following minimum health requirements: 1. The drinking fountain bubbler shall be on an ☒ ☐ ☐ angle which prevents waste water from flowing over the drinking fountain bubbler. 2. Water flow shall be actuated by mechanical means. ☒ ☐ ☐ 1231.3.4 Showers Must be available to all inmates on a ratio of at least one shower to every 20 inmates or fraction thereof and ☒ ☐ ☐ must provide hot and cold water or tempered water. Shower stalls/shower areas must be designed and constructed of materials which are impervious to water ☒ ☐ ☐ and soap so they may be easily cleaned. Shower areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.5 Beds Must be elevated off the floor, have a solid bottom, and a sleeping surface of at least 30 inches (762 mm) wide ☒ ☐ ☐ and 76 inches (1930 mm) long. Multiple beds must have a minimum of 21 inches (533 mm) between bed pans. ☒ ☐ ☐ Except in minimum security areas, beds must be securely fastened to the floor or the wall. ☒ ☐ ☐ 1231.3.6 Lighting. Lighting in housing units, dayrooms and activity areas must be sufficient to permit easy reading by a person with normal vision, and shall not be less than 20 ☒ ☐ ☐ footcandles (215.2 lux) at desk level and in the grooming area. Lighting shall be centrally controlled and/or occupant controlled in housing cells or rooms. ☒ ☐ ☐ Night lighting in these areas shall be sufficient to give good visibility for purposes of supervision ☒ ☐ ☐ In minimum-security areas, lighting may be supplied by ordinary lighting fixtures, and in areas of higher ☒ ☐ ☐ security, light fixtures must be of secure design. 1231.3.7 Windows. In housing areas of higher than minimum security, exterior windows which are constantly accessible to inmates for escape must be designed and constructed ☒ ☐ ☐ so that if broken out, the net area accessible for escape is no greater than 5 inches (127 mm) in one dimension. 1231.3.8 Cell padding. No sobering cells at this facility. In sobering cells, the floor and partition shall be padded. ☐ ☐ ☒ In safety cells, padding must cover the entire floor, doors, and walls and everything on them to a clear ☐ ☐ ☒ height of 8 feet (2438 mm). All such padded cells must be equipped with a tamper resistant fire sprinkler as approved by the State Fire Marshal. ☐ ☐ ☒ All padding must be: 1. Approved for use by the State Fire Marshal; ☐ ☐ ☒ 5735 Stanislaus REACT Center II PHY 23-24 - 8 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 2. Nonporous to facilitate cleaning; ☐ ☐ ☒ 3. At least 1/2-inch (12.7 mm) thick; ☐ ☐ ☒ 4. Of a unitary or laminated construction to prevent its destruction by teeth, hand tearing or small metal ☐ ☐ ☒ objects; 5. Firmly bonded to all padded surfaces to prevent tearing or ripping; and ☐ ☐ ☒ 6. Without any exposed seams susceptible to tearing or ripping. ☐ ☐ ☒ 1231.3.9 Mirrors. A mirror of a material appropriate to the level of security must be provided near each wash basin specified in ☒ ☐ ☐ these regulations. 1231.3.10 Seating. In temporary holding and temporary staging cells, ☒ ☐ ☐ seating must be securely fixed to the floor and/or wall. When bench seating is used, 18 inches (457 mm) of bench is seating for one person. ☒ ☐ ☐ 1231.3.11 Table/seat. In single- and double-occupancy cells, a table and seat for the purpose of writing and dining shall be provided. ☒ ☐ ☐ Exception: A Type I facility does not require a table and a seat. 1231.3.12 Weapons locker. A secure weapons locker shall be located outside the ☒ ☐ ☐ security perimeter of the facility Such weapons lockers shall be equipped with individual compartments, each with an individual locking device. ☒ ☐ ☐ Weapons lockers are required in temporary and court holding facilities and in all facilities of higher than ☒ ☐ ☐ minimum security. Design Requirements (102(c)6) Design requirements as specified in Title 24, Part 1, 102(c)6 are met. (See regulation for specific requirements. Note areas of non-compliance that are ☒ ☐ ☐ applicable to the facility type and construction date in the "comments" section.) 5735 Stanislaus REACT Center II PHY 23-24 - 9 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TYPE II AND III FACILITIES Board of State and Community Corrections PROCEDURES1 BSCC Code: 5743 FACILITY NAME: Stanislaus Public Safety Center Units 1 & 2 FACILITY TYPE: II PERSON(S) INTERVIEWED: Lt. Wright, Sgt. Kielberg, Sgt. Ballard, Dep. Griffin, Dep. Delgadillo FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS 1027.5 SAFETY CHECKS SCSDPPMADD 9-01.01 Security Inspections SCSDPPMADD 9-01.06 Electronic The facility administrator shall develop and implement Documentation System policy and procedures for conducting safety checks that include, but are not limited to, the following: ☒ ☐ ☐ Only PSC Unit 2 was in operation at the time (a) Safety checks will determine the safety and well- of inspection. being of individuals and shall be conducted at least hourly through direct visual observation of all people held and housed in the facility. (b) There shall be no more than a 60-minute lapse Three consecutive months of safety checks between safety checks. documentation was requested for this ☒ ☐ ☐ inspection. Of those safety checks reviewed, the overwhelming majority of them were within a 60-minute lapse of the previous one. (c) Safety checks for people in sobering cells, safety cells, and restraints shall occur more frequently as ☒ ☐ ☐ outlined in section 1055, section 1056, and section 1058 of these regulations. (d) Safety checks shall occur at random or varied ☒ ☐ ☐ intervals. (e) There shall be a written plan that includes the documentation of all safety checks. Documentation shall include: ☒ ☐ ☐ (1) the actual time at which each individual safety check occurred; (2) the location where each individual safety check occurred, such as a cell, module, or dormitory ☒ ☐ ☐ number; and, (3) Initials or employee identification number of staff ☒ ☐ ☐ who completed the safety check(s). 1 This document is intended for use as a tool during the targeted inspection process; this worksheet may not contain each Title 15 regulation that is required. Additionally, many regulations on this worksheet are SUMMARIES of the regulation; the text on this worksheet may not contain the entire text of the actual regulation. Please refer to the complete California Code of Regulations, Title 15, Minimum Standards for Local Facilities, Division 1, Chapter 1, Subchapter 4 for the complete list and text of regulations. 5743 Stanislaus Public Safety Center Units 1 & 2 II PRO 23-24 Page 1 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (f) A documented process by which safety checks are reviewed at regular defined intervals by a supervisor or facility manager, including methods of mitigating ☒ ☐ ☐ patterns of inconsistent documentation, or untimely completion of, safety checks. 1032 FIRE SUPPRESSION PREPLANNING SCSDPPMADD 10-01.01 Fire Suppression Planning Pursuant to Penal Code Section 6031.1(b), the facility administrator shall consult with the local fire department ☒ ☐ ☐ having jurisdiction over the facility, with the State Fire Marshal, or both, in developing a plan for fire suppression which shall include, but not be limited to: (a) a fire suppression pre-plan developed with the local fire department to be included as part of the policy and ☒ ☐ ☐ procedures manual (Title 15, California Code of Regulations Section 1029); (b) monthly fire prevention inspections by facility staff ☒ ☐ ☐ with two-year retention of the inspection record; (c) fire prevention inspections as required by Health and Safety Code Section 13146.1(a) and (b) which requires ☒ ☐ ☐ inspections at least once every two years; (d) an evacuation plan; and, ☒ ☐ ☐ (e) a plan for the emergency housing of incarcerated ☒ ☐ ☐ people in the case of fire. 1056 USE OF SOBERING CELL This facility does not have sobering cells. The sobering cell described in Title 24, Part 2, Section ☐ ☐ ☒ 1231.2.4, shall be used for temporary holding of incarcerated people who are a threat to their own safety or the safety of others due to their state of intoxication. A person shall be removed from the sobering cell as soon as they are able to continue the admission process ☐ ☐ ☒ or are no longer a risk to themselves or others. In no case shall a person remain in a sobering cell over six hours without an evaluation by medical or custody staff to determine whether the person has an urgent ☐ ☐ ☒ medical problem, pursuant to section 1213 of these regulations. At 12 hours from the time of placement, all persons must ☐ ☐ ☒ receive an evaluation by responsible health care staff. Intermittent direct visual observation of people held in the sobering cell shall be conducted no less than every ☐ ☐ ☒ half hour. Such observation shall be documented. 5743 Stanislaus Public Safety Center Units 1 & 2 II PRO 23-24 Page 2 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS 1058 USE OF RESTRAINT DEVICES This facility does not use restraints. The facility administrator, in cooperation with the responsible physician, shall develop and implement written policies and procedures for the use of restraint devices. Restraint devices include any devices which immobilize extremities or prevent the incarcerated ☐ ☐ ☒ person from being ambulatory. The provisions of this section do not apply to the use of handcuffs, shackles, or other restraint devices when used to restrain incarcerated people for security reasons. The facility manager may delegate authority to place an incarcerated person in restraints to responsible health care staff. (a) The policy shall address the following areas: ☐ ☐ ☒ (1) acceptable restraint devices; (2) signs or symptoms which should result in immediate medical/mental health referral; ☐ ☐ ☒ availability of cardiopulmonary resuscitation equipment; (3) protective housing of restrained persons; ☐ ☐ ☒ (4) provision for hydration and sanitation needs; and, ☐ ☐ ☒ (5) exercising of extremities. ☐ ☐ ☒ (b) Policy shall also include, but not be limited to, the following requirements: ☐ ☐ ☒ (1) In no case shall restraints be used for punishment or as a substitute for treatment. (2) Restraint devices shall only be used on incarcerated people who display behavior which ☐ ☐ ☒ results in the destruction of property or reveal an intent to cause physical harm to self or others. (3) Restraint devices should be used only when less restrictive alternatives, including verbal de- ☐ ☐ ☒ escalation techniques, have been attempted and are deemed ineffective. (4) An incarcerated person shall be placed in restraints only with the approval of the facility manager, the facility watch commander, or ☐ ☐ ☒ responsible health care staff; continued retention shall be reviewed a minimum of every hour. (5) Continuous direct visual observation shall be ☐ ☐ ☒ maintained until a medical opinion can be obtained. (6) A medical opinion on placement and retention shall be secured within one hour from the time of ☐ ☐ ☒ placement. (7) A medical assessment shall be completed within ☐ ☐ ☒ four hours of placement. 5743 Stanislaus Public Safety Center Units 1 & 2 II PRO 23-24 Page 3 of 4 A353 Type II & III Targeted PRO eff 01.2024 TITLE 15 SECTION YES NO N/A P/P REFERENCE – COMMENTS (8) Continuous direct visual observation shall be conducted at least twice every 30 minutes to ensure that the restraints are properly employed, and to ensure the safety and well-being of the incarcerated person. Such observation shall be documented. ☐ ☐ ☒ While in restraint devices all incarcerated persons shall be housed alone or in a specified housing area which makes provisions to protect the person from abuse. (9) If the facility manager, or designee, in consultation with responsible health care staff determines that an incarcerated person cannot be ☐ ☐ ☒ safely removed from restraints after eight hours, the person shall be taken to a medical facility for further evaluation. (10) Where applicable, the facility manager shall use the restraint device manufacturer’s recommended ☐ ☐ ☒ maximum time limits for placement. (11) All events and information related to the placement in restraints shall be documented and shall be video recorded unless exigent circumstances prevent staff from doing so. The ☐ ☐ ☒ documentation shall include: the reason for placement; person authorizing placement; names of staff involved in the placement; injuries sustained; and the duration of placement. 1065 EXERCISE AND OUT OF CELL TIME SCSDPPMADD 04-01.25 Yard Deputy (a) The facility administrator of a Type II or III facility shall This facility is of modular design and access ☒ ☐ ☐ develop written policies and procedures for a minimum to the dayrooms is based on tier level. Each of 10 hours of out of cell time distributed over a period of tier has access to the dayroom for seven days to include: approximately four hours per day. (1) an opportunity for three hours of exercise and A review of the times for the exercise yard was conducted. Three hours per week are ☒ ☐ ☐ allowed for access to the exercise yard. This is consistently reviewed by the Sergeant. (2) an opportunity for seven hours of recreation. ☒ ☐ ☐ Policies shall include reasonable and necessary ☒ ☐ ☐ procedures to ensure safety and security. 5743 Stanislaus Public Safety Center Units 1 & 2 II PRO 23-24 Page 4 of 4 A353 Type II & III Targeted PRO eff 01.2024 ADULT DETENTION FACILITY LIVING AREA SPACE EVALUATION Board of State and Community Corrections BSCC Code: 5743 FACILITY: Stanislaus Public Safety Center Units 1 & 2 TYPE: II RC: 384 FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 ROOMS EACH ROOM Applicabl EACH CELL FIXTURES* Cell # Total DIMENSIONS Location e Type Cells # Beds RC RC (L x W x H) T U W F S Standards UNIT 1 (23-24) Not used, no inmates housed. Fire suppression inspections are conducted monthly and biennial fire inspections are completed. A Module Lower Level Bathroom 4 4 1 4 A1-3 Dorm 1988 3 4 4 12 19.0’x11.5’ Irregular; approx A4 & A5 Dorm 1988 2 4 4 8 300 sq. ft. A6-8 Dorm 1988 3 4 4 12 19.0’x11.5’ 18-20 Open dormitory. Bathrooms are located on each level. Mezzanine Bathroom 4 4 1 4 A9-11 Dorm 1988 3 4 4 12 19.0’x11.5’ Irregular; approx A12 & A13 Dorm 1988 2 4 4 8 300 sq. ft. A14-16 Dorm 1988 3 4 4 12 19.0’x11.5’ B Module Lower level – Male Housing Bathroom 4 4 1 4 B1-3 Dorm 1988 3 4 4 12 19.0’x11.5’ Irregular; approx B4 & B5 Dorm 1988 2 4 4 8 300 sq. ft. B6-8 Dorm 1988 3 4 4 12 19.0’x11.5’ 18-20 Open dormitory. Bathrooms are located on each level. Mezzanine – Male Housing Bathroom 4 4 1 4 B9-11 Dorm 1988 3 4 4 12 19.0’x11.5’ Irregular; approx B12 & B13 Dorm 1988 2 4 4 4 300 sq. ft. B14-16 Dorm 1988 3 4 4 12 19.0’x11.5’ 18-20 Open dormitory. Bathrooms are located on each level. C Module Lower level Bathroom 4 4 1 4 C1-3 Dorm 1988 3 4 4 12 19.0’x11.5’ Irregular; approx C4 & C5 Dorm 1988 2 4 4 8 300 sq. ft. C6-8 Dorm 1988 3 4 4 12 19.0’x11.5’ 18-20 Open dormitory. Bathrooms are located on each level. Mezzanine Bathroom 4 4 1 4 C9-11 Dorm 1988 3 4 4 12 19.0’x11.5’ *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5743 Stanislaus Public Safety Center Units 1 & 2 II LASE 23-24 - 1 - A360 LAS Adult-05.dot (8/05) ROOMS EACH ROOM Applicabl EACH CELL FIXTURES* Cell # Total DIMENSIONS Location e Type Cells # Beds RC RC (L x W x H) T U W F S Standards C12 & C Irregular; approx Dorm 1988 2 4 4 8 13 300 sq. ft. C14-16 Dorm 1988 3 4 4 12 19.0’x11.5’ Unit 2 A Module Lower Level A1 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 A2 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 A Module Mezzanine Level A3 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 A4 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 (23-24) A-Module has a common dayroom of approximately 2788 sq. ft. with 1 fountain. B Module Lower Level B1 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 B2 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 B Module Mezzanine Level B3 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 B4 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 (23-24) B-Module has a common dayroom of approximately 2788 sq. ft. with 1 fountain. C Module Lower Level C1 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 C2 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 C Module Mezzanine Level C3 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 C4 Dorm 2008 1 16 16 16 20’x28’ 2 2 1 (23-24) C-Module has a common dayroom of approximately 2788 sq. ft. with 1 fountain. One large exercise yard detached from the unit with a toilet and water available. *T = Toilets; U = Urinals; W = Wash Basins; F = Fountains; S = Showers in unit. If "Total RC" appears in brackets ( ), it is not part of the facility's rated capacity. "+" indicates that capacity includes prorated air space from adjacent areas. 5743 Stanislaus Public Safety Center Units 1 & 2 II LASE 23-24 - 2 - A360 LAS Adult-05.dot (8/05) ADULT TYPE I, II, III AND IV FACILITIES PHYSICAL PLANT EVALUATION The Board of State and Community Corrections APPLICABLE TITLE 24 REGULATIONS: 6/94; 2/99; 2001; 2005; 2008; 2010, 2013, 2017 BSCC Code: 5743 FACILITY NAME: Stanislaus Public Safety Center Units 1 & 2 FACILITY TYPE: II 6/94: 2/99: 2001: 2005: 2008: 2010: ☐ ☐ ☐ ☐ ☒ ☐ APPLICABLE REGULATIONS (Check All That Apply): 2013: ☐ 2017: ☐ 5/88 ☐ ☐ ☐ ☒ FIELD REPRESENTATIVE: Tim McWilliams DATE: 04/23/24 TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.1 Reception and booking. Prisoners booked at the Sheriff’s Detention Facilities where booking and housing occur shall have Center East facility are then transferred to the following space and equipment: Units 1 & 2. ☐ ☐ ☒ 1. Weapons locker as specified in Section 1231.3.12. 2. A cell or room for the confinement of inmates pending their booking, complying with Section ☐ ☐ ☒ 1231.2.2. 3. A sobering cell as described in Section 1231.2.4 if intoxicated, inmates who may pose a danger to ☐ ☐ ☒ themselves or others are held. For those facilities that accept male and female intoxicated inmates two sobering cells shall be ☐ ☐ ☒ provided. 4. Access to a shower within the secure portion of the facility. ☐ ☐ ☒ 5. Provide access to a secure vault or storage When an inmate is transferred to this facility space for inmate valuables. their personal property follows them and is secured in a storage area. At the time of ☒ ☐ ☐ release, the inmate is returned all the property they had at booking. 1231.2.2 Temporary holding cell or room. No temporary holding cells at this facility. A temporary holding cell or room shall: 1. Contain a minimum of 10 square feet (0.93 m2) ☐ ☐ ☒ of floor area per inmate; 2. Be limited to no more than 16 inmates; ☐ ☐ ☒ 3. Be no smaller than 40 square feet (3.7 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☐ ☐ ☒ more; 4. Contain seating to accommodate all inmates as required in Section 1231.3; ☐ ☐ ☒ 5. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☐ ☐ ☒ 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 1 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 6. Maximize visual supervision of inmates by staff; and ☐ ☐ ☒ 7. When located in a temporary holding facility, the cell or room shall be equipped with a bunk if inmates are to be held longer than 12 hours. ☐ ☐ ☒ 1231.2.3 Temporary staging cell or room. No temporary staging cells at this facility. A temporary staging cell or room shall: 1. Be constructed for the purpose of holding inmates who have been classified and segregated ☐ ☐ ☒ in accordance with Sections 1050 and 1053 of Title 15, Division 1, California Code of Regulations. 2. Be limited to holding inmates up to four hours. ☐ ☐ ☒ 3. Be limited to no more than 80 inmates. ☐ ☐ ☒ 4. Contain a minimum of 10 square feet (0.93 m2) of floor area per inmate and a clear ceiling height of ☐ ☐ ☒ 8 feet (2438 mm) or more. 5. Be no smaller than 160 square feet (14.9 m2). No temporary staging cells at this facility. ☐ ☐ ☒ 6. Contain seating to accommodate all inmates as required in Section 1231.3. ☐ ☐ ☒ 7. Contain toilet, wash basin and drinking fountain as specified in Section 1231.3. ☐ ☐ ☒ 8. Maximize visual supervision of inmates by staff. ☐ ☐ ☒ 1231.2.4 Sobering cell. No cells of this type at this facility. A sobering cell shall: 1. Contain a minimum of 20 square feet (1.9 m2) of ☐ ☐ ☒ floor area per inmate; 2. Be limited to eight inmates; ☐ ☐ ☒ 3. Be no smaller than 60 square feet (5.6 m2) and have a clear ceiling height of 8 feet (2438 mm) or ☐ ☐ ☒ more; 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; ☐ ☐ ☒ 5. Have padded partitions located next to toilet fixture in such a manner that they provide support ☐ ☐ ☒ to the user; 6. Maximize visual supervision of inmates by staff; ☐ ☐ ☒ 7. Be padded on the floor as specified in Section 1231.3; and, ☐ ☐ ☒ 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 2 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 8. Have accessible a shower in the secure portion of the facility. ☐ ☐ ☒ 1231.2.5 Safety cell. No cells of this type at this facility. A safety cell shall: 1. Contain a minimum of 48 square feet (4.5 m2) of floor area with no one floor dimension being less ☐ ☐ ☒ than 6 feet (1829 mm) and a clear ceiling height of 8 feet (2438 mm) or more; 2. Be limited to one inmate; ☐ ☐ ☒ 3. Contain a flushing ring toilet, capable of accepting solid waste, mounted flush with the floor, the controls for which must be located outside of the ☐ ☐ ☒ cell; 4. Be padded as specified in Section 1231.3; ☐ ☐ ☒ 5. Be equipped with a variable intensity, security- type lighting fixture which is inaccessible to the inmate occupant, control of which is located outside ☐ ☐ ☒ of the cell; 6. Provide one or more vertical view panels not more than 4 inches (102 mm) wide nor less than 24 inches (610 mm) long which shall provide a view of ☐ ☐ ☒ the entire room; 7. Provide a food pass with lockable shutter, no more than 4 inches (102 mm) high, and located between 26 inches (660 mm) and 32 inches (813 ☐ ☐ ☒ mm) as measured from the bottom of the food pass to the floor; and, 8. Any wall or ceiling mounted devices must be inaccessible to the inmate occupant. ☐ ☐ ☒ 1231.2.6 Single-occupancy cells. No single-occupancy cells at this facility. Single-occupancy cells shall: ☐ ☐ ☒ 1. Have a maximum capacity of one inmate; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☐ ☐ ☒ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☐ ☐ ☒ mm); 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☐ ☐ ☒ 5. Contain a bunk, desk and seat as specified in Section 1231.3. ☐ ☐ ☒ Exception: A Type I facility does not require a desk and seat. 1231.2.7 Double-occupancy cells. No double-occupancy cells at this facility. Double-occupancy cells shall: ☐ ☐ ☒ 1. Have a maximum capacity of two inmates; 2. Contain a minimum of 60 square feet (5.6 m2) of floor area in Type I facilities and 70 square feet (6.5 ☐ ☐ ☒ m2) of floor area in Type II and Type III facilities; 3. Have a minimum clear ceiling height of 8 feet (2438 mm) and a minimum width of 6 feet (1829 ☐ ☐ ☒ mm); 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 3 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 4. Contain a toilet, wash basin and drinking fountain as specified in Section 1231.3; and ☐ ☐ ☒ 5. Contain two bunks, and at least one desk and seat as specified in Section 1231.3. ☐ ☐ ☒ Exception: A Type I facility does not require a desk and seat. 1231.2.8 Dormitories. Only Unit 2 is open. Unit 1 is closed. Dormitories shall: 1. Contain a minimum of 50 square feet (4.7 m2) of floor area per inmate for a single-bed unit; a minimum of 70 square feet (7 m2) for a double-bed ☒ ☐ ☐ unit; and a minimum of 90 square feet (9.3 m2) for triple-bed unit and have a minimum ceiling height of 8 feet (2438 mm); 2. Be designed for no more than 64 inmates and no fewer than four inmates; ☒ ☐ ☐ 3. Provide access to water closets separate from the wash basin and drinking fountains as specified ☒ ☐ ☐ in Section 1231.3; and 4. In other than Type I facilities, provide storage space for personal items and clothing for each ☒ ☐ ☐ occupant. 1231.2.9 Dayrooms. Dayrooms or dayroom space shall: 1. Contain 35 square feet (3.3 m2) of floor area per ☒ ☐ ☐ inmate in width in front of cells/rooms; 2. Contain tables and seating to accommodate the 11 tables total; 6 seats at 9 tables and 5 maximum number of inmates; ☒ ☐ ☐ seats at 2 tables, to allow for ADA. 3. Provide access to water closets, wash basins and drinking fountains as specified in Section ☒ ☐ ☐ 1231.3; 4. Provide access to a shower or showers as specified in Section 1231.3; and ☒ ☐ ☐ 5. Be provided to all inmates in Type II and Type III facilities (except those housed in special-use cells) and to inmate workers in Type I facilities. Dayroom space as described in this section may be a part of a single occupancy cell used for administrative ☒ ☐ ☐ segregation or a dormitory, in which case the floor area of the cell or a dormitory must be increased by the square footage required for the dayroom. 1231.2.10 Exercise area. An outdoor exercise area or areas must be provided in every Type II and Type III facility. The minimum clear height must be 15 feet (4572 mm) and the minimum number of square feet of surface area will be computed ☒ ☐ ☐ by multiplying 80 percent of maximum rated population by 50 square feet (4.7 m2) and dividing the result by the number of one-hour exercise periods per day. The exercise area must contain or provide free access A portable toilet has been placed in the yard. to a toilet, wash basin, and drinking fountain as Water is available. ☒ ☐ ☐ provided in Section 1231.3. 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 4 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS There must be at least one exercise area of not less than 600 square feet (55.7 m2). The design shall facilitate security and supervision appropriate to the ☒ ☐ ☐ level of custody. Type IV facilities shall have an outdoor recreation area or access to community recreation facilities. ☐ ☐ ☒ 1231.2.11 Correctional program/multipurpose space. An area for correctional programming must be provided in every Type II and Type III facility. The program area ☒ ☐ ☐ and furnishings shall be designed to meet the needs specified by the facility’s program statement. Type IV facilities shall have multipurpose space for games and activities, dining, visiting, TV meetings and quiet space for study and reading, such that activities ☐ ☐ ☒ do not conflict with each other. 1231.2.12 Medical examination room. There must be a minimum of one suitably equipped medical examination room in every facility which provides on-site health care. The examination room shall be designed in consultation with the responsible ☒ ☐ ☐ physician/health authority. Such a medical examination room shall: 1. Be located within the security area and provide for privacy of the inmates; ☒ ☐ ☐ 2. Provide not less than 100 square feet (9.3 m2) of floor space with no single dimension less than 7 feet ☒ ☐ ☐ (2134 mm); 3. Provide hot and cold running water; ☒ ☐ ☐ 4. Provide lockable storage for medical supplies; ☒ ☐ ☐ 5. Provide an examination table; ☒ ☐ ☐ 6. Provide adequate lighting; and ☒ ☐ ☐ 7. Any room where medical procedures are provided must be equipped with hot and cold ☒ ☐ ☐ running water 1231.2.13 Pharmaceutical storage space. Located at the Sheriff's Detention Facility Provide lockable storage space for medical (East). supplies and pharmaceutical preparations as ☐ ☐ ☒ referenced by Title 15, California Code of Regulations, Section 1216. 1231.2.14 Medical care housing. Inmates in need of medical housing will be There shall be some means to provide medical care transported to the Sheriff's Detention Facility and housing of ill and/or infirm inmates. ☐ ☐ ☒ (East). No medical care housing at this facility. When the program statement for a Type II or Type III facility indicates that medical care housing is needed, such housing must provide lockable storage space for medical instruments and must be located within the ☐ ☐ ☒ security area of the facility accessible to both female and male inmates, but not in the living area of either. The medical care housing unit shall be designed in consultation with the health authority. ☐ ☐ ☒ Medical/mental health areas may contain other than single occupancy cells. ☐ ☐ ☒ 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 5 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS If negative pressure isolation rooms are being planned, they shall be designed to recognized industry ☐ ☐ ☒ standards. 1231.2.16 Commissary. In all Type II, III and IV facilities, except where community access is available, there shall be provisions made for inmates to purchase items (such ☒ ☐ ☐ as candy, toilet articles, stationery supplies, books, newspapers and magazines, etc.). An area shall be provided for the secure storage of the stock for such inmate canteen items. ☒ ☐ ☐ 1231.2.17 Dining facilities. Meals are provided inside the housing units. In all Type II, III and IV facilities which serve meals, dining areas shall be provided which will allow groups ☒ ☐ ☐ of inmates to dine together. Such dining areas shall not contain toilets, wash basins or showers in the same room without appropriate visual ☒ ☐ ☐ barrier. Wherever the facility contains a central dining room or rooms, it shall contain a minimum of 15 square feet (1.4 m2) of floor space and sufficient tables and seating for ☐ ☐ ☒ each inmate being fed. 1231.2.18 Visiting space. Space shall be provided in all Types I, II, III and IV ☒ ☐ ☐ facilities for visiting. 1231.2.19 Safety equipment storage. A secure area shall be provided for the storage of safety equipment such as fire extinguishers, self-contained ☒ ☐ ☐ breathing apparatus, wire and barcutters, emergency lights, etc.. 1231.2.20 Janitors’ closet. In Type II facilities, at least one securely lockable janitors’ closet with sufficient area for the storage of ☒ ☐ ☐ cleaning implements and supplies must be provided within the security areas of the facility A mop sink shall also be available within the security area of the facility. In court holding, temporary holding, Types I, III and IV facilities, the closet need not be in the ☒ ☐ ☐ security area. 1231.2.21 Storage rooms. One or more storage rooms shall be provided to accommodate a minimum of 80 cubic feet (2.3 m3) of storage area per inmate for inmate clothing and personal property, institutional clothing, bedding and ☒ ☐ ☐ supplies. Court holding, temporary holding and Type I facilities may be excluded from the storage space requirement for personal and institutional clothing unless clothing is issued. 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 6 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.2.22 Audio monitoring system. Audio is available in the dayroom and In court holding, temporary holding, Type I, Type II and dormitories. Type II facilities there shall be an inmate- or sound- actuated audio monitoring system in temporary holding cells or rooms, temporary staging cells or rooms, sobering cells, safety cells, single and double ☒ ☐ ☐ occupancy cells, dormitories, dayrooms, exercise areas and correctional program/multipurpose space, which is capable of alerting personnel who can respond immediately. 1231.2.23 Laundry facilities. Not located at this facility. In Type IV facilities, provision shall be made for washing and drying personal clothing by machines, ☐ ☐ ☒ either in the facility or in the community, if access is permitted for same. 1231.2.24 Emergency power. There shall be a source of emergency power in all detention facilities capable of providing minimal lighting in all housing units, activities areas, corridors, stairs and ☒ ☐ ☐ central control points, and to maintain fire and life safety, security, communications and alarm systems. Such an emergency power source shall conform to the requirements specified in Title 24, Part 3, Article 700, California Electrical Code, California Code of ☒ ☐ ☐ Regulations. 1231.2.25 Confidential interview rooms. There must be a minimum of one suitably furnished interview room for confidential interviews in every facility which provides onsite health care. The interview room shall be designed in consultation with responsible ☒ ☐ ☐ custodial staff and health care staff. Such an interview room shall: 1. Be located within the security area accessible to both female and male inmates; and ☒ ☐ ☐ 2. Provide not less than 70 square feet (6.5 m2) of 8’7” x 9’4”. floor space with no single dimension less than 6 feet 10’7” x 8’6”. ☒ ☐ ☐ (1829 mm). 1231.2.26 Attorney interview space. All facilities except Type IV facilities shall include attorney interview areas which provide for ☒ ☐ ☐ confidential consultation with inmates. 1231.3.1 Toilets/urinals. No single or double cells at this facility. 1. Toilets/urinals must be provided in single- ☐ ☐ ☒ occupancy cells and double-occupancy cells. 2. In dormitories, toilets/urinals must be provided in a ratio to inmates of 1:10. ☒ ☐ ☐ 3. Toilets/urinals must be accessible to the occupants of day-rooms and exercise areas. ☒ ☐ ☐ 4. In temporary holding cells and temporary staging No temporary holding or staging cells at this cells toilets/urinals must be provided in a ratio to facility. ☐ ☐ ☒ inmates of 1:16. 5. In sobering cells toilets/urinals must be provided No sobering cells are located at this facility. in a ratio to inmates of 1:8. ☐ ☐ ☒ 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 7 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 6. One urinal or 2 feet (610 mm) of urinal trough may be substituted for each toilet up to one third of the total number of toilets required, except in those ☐ ☐ ☒ facilities or portions thereof used for females. 7. Toilet areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.2 Wash basins. No single or double cells at this facility. 1. Wash basins must be provided in single ☐ ☐ ☒ occupancy cells and double occupancy cells. 2. In dormitories, wash basins must be provided in a ratio to inmates of 1:10. ☒ ☐ ☐ 3. Wash basins must be accessible to the occupants of day-rooms and exercise areas ☒ ☐ ☐ 4. In temporary holding cells and temporary staging No holding cells or temporary staging cells at cells, wash basins must be provided in a ratio to this facility. ☐ ☐ ☒ inmates of 1:16. 5. In sobering cells, wash basins must be provided No sobering cells at this facility. in a ratio to inmates of 1:8. ☐ ☐ ☒ 6. Wash basins must be provided with hot and cold or tempered water. ☒ ☐ ☐ 7. Two feet (610 mm) of wash basin trough may be substituted for each basin required. ☐ ☐ ☒ 1231.3.3 Drinking fountains. There must be a minimum of one drinking fountain in every single-occupancy cell, double-occupancy cell, dormitory, temporary holding cell, temporary staging ☒ ☐ ☐ cell, sobering cell, and be accessible to the occupants of day rooms and exercise areas. Additional drinking fountains shall be located in other areas of the facility so that drinking water will be ☒ ☐ ☐ available to inmates and staff. Such drinking fountains must meet the following minimum health requirements: 1. The drinking fountain bubbler shall be on an ☒ ☐ ☐ angle which prevents waste water from flowing over the drinking fountain bubbler. 2. Water flow shall be actuated by mechanical means. ☒ ☐ ☐ 1231.3.4 Showers Must be available to all inmates on a ratio of at least one shower to every 20 inmates or fraction thereof and ☒ ☐ ☐ must provide hot and cold water or tempered water. Shower stalls/shower areas must be designed and constructed of materials which are impervious to water ☒ ☐ ☐ and soap so they may be easily cleaned. Shower areas shall provide modesty for inmates with staff being able to visually supervise. ☒ ☐ ☐ 1231.3.5 Beds Must be elevated off the floor, have a solid bottom, and a sleeping surface of at least 30 inches (762 mm) wide ☒ ☐ ☐ and 76 inches (1930 mm) long. Multiple beds must have a minimum of 21 inches (533 mm) between bed pans. ☒ ☐ ☐ Except in minimum security areas, beds must be securely fastened to the floor or the wall. ☒ ☐ ☐ 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 8 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.3.6 Lighting. Lighting in housing units, dayrooms and activity areas must be sufficient to permit easy reading by a person with normal vision, and shall not be less than 20 ☒ ☐ ☐ footcandles (215.2 lux) at desk level and in the grooming area. Lighting shall be centrally controlled and/or occupant controlled in housing cells or rooms. ☒ ☐ ☐ Night lighting in these areas shall be sufficient to give good visibility for purposes of supervision ☒ ☐ ☐ In minimum-security areas, lighting may be supplied by ordinary lighting fixtures, and in areas of higher ☒ ☐ ☐ security, light fixtures must be of secure design. 1231.3.7 Windows. In housing areas of higher than minimum security, exterior windows which are constantly accessible to inmates for escape must be designed and constructed ☒ ☐ ☐ so that if broken out, the net area accessible for escape is no greater than 5 inches (127 mm) in one dimension. 1231.3.8 Cell padding. No sobering or safety cells at this facility. In sobering cells, the floor and partition shall be padded. ☐ ☐ ☒ In safety cells, padding must cover the entire floor, doors, and walls and everything on them to a clear ☐ ☐ ☒ height of 8 feet (2438 mm). All such padded cells must be equipped with a tamper resistant fire sprinkler as approved by the State Fire Marshal. ☐ ☐ ☒ All padding must be: 1. Approved for use by the State Fire Marshal; ☐ ☐ ☒ 2. Nonporous to facilitate cleaning; ☐ ☐ ☒ 3. At least 1/2-inch (12.7 mm) thick; ☐ ☐ ☒ 4. Of a unitary or laminated construction to prevent its destruction by teeth, hand tearing or small metal ☐ ☐ ☒ objects; 5. Firmly bonded to all padded surfaces to prevent tearing or ripping; and ☐ ☐ ☒ 6. Without any exposed seams susceptible to tearing or ripping. ☐ ☐ ☒ 1231.3.9 Mirrors. A mirror of a material appropriate to the level of security must be provided near each wash basin specified in ☒ ☐ ☐ these regulations. 1231.3.10 Seating. In temporary holding and temporary staging cells, ☐ ☐ ☒ seating must be securely fixed to the floor and/or wall. When bench seating is used, 18 inches (457 mm) of bench is seating for one person. ☐ ☐ ☒ 1231.3.11 Table/seat. In single- and double-occupancy cells, a table and seat for the purpose of writing and dining shall be provided. ☐ ☐ ☒ Exception: A Type I facility does not require a table and a seat. 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 9 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19) TITLE 24 SECTION YES NO N/A COMMENTS 1231.3.12 Weapons locker. A secure weapons locker shall be located outside the ☒ ☐ ☐ security perimeter of the facility. Such weapons lockers shall be equipped with individual compartments, each with an individual locking device. ☒ ☐ ☐ Weapons lockers are required in temporary and court holding facilities and in all facilities of higher than ☒ ☐ ☐ minimum security. Design Requirements (102(c)6) Design requirements as specified in Title 24, Part 1, 102(c)6 are met. (See regulation for specific requirements. Note areas of non-compliance that are ☒ ☐ ☐ applicable to the facility type and construction date in the "comments" section.) 5743 Stanislaus Public Safety Center Units 1 & 2 II PHY 23-24 - 10 - A383 PHY Type I-IV 94 99 01 05 08 10 13 17.dot (1/19)